Noise - Mitsubishi Electric Mr.SLIM PUH-P1VGAA Technical & Service Manual

Split-type, heat pump air conditioners split-type, air conditioners
Hide thumbs Also See for Mr.SLIM PUH-P1VGAA:
Table of Contents

Advertisement

Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan(drive) o No.
Fan
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor
: D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 3 phase 415V 50Hz
kW
A
A
kW
W
kW
K/min(CFM)
Cooling
dB
W
mm(in.)
D
mm(in.)
H
mm(in.)
kg(lbs)
kg(lbs)
L
Liquid
mm(in.)
Gas
mm(in.)
Indoor side
Outdoor side
Height difference
Piping length
Indoor
Outdoor
D.B. 35˚C , W.B.22.5˚C
D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
PU-P5YGAA
.UK
2
Cooling
3-ph, 50Hz, 380/400/415V(4wires)
4.70
7.60
65.5
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
BE82YADMT
3.5
Line start
Thermal relay, HP switch, Discharge thermo
38
Plate fin coil
Propeller (direct) o 2
0.07+0.07
95(3,360)
55
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
125(276)
R407C
4.6(10.1)
1.7 (Ester) MEL56
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
16
PU-P6YGAA
.UK
2
Cooling
5.58
9.03
74
BE96YADMT
4.2
100(3,530)
57
4.9(10.8)