9

WIRING SPECIFICATIONS

WIRING SPECIFICATIONS FOR 220~240V 50Hz
(INDOOR-OUTDOOR CONNECTING CABLE)
Wire size
Cross section
of cable
Round
Flat
Flat
Round
1 : Power supply cords of appliances shall not be lighter than design 245 IEC or 227 IEC.
2 : In case that cable with stripe of yellow and green is available.
3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
4 : In case of regular polarity connection (S1-S2-S3).
5 : In the flat cables are connected as this picture, they can be used up to 80m.
S1 S2 S3
6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, Humidity or materials, etc.
Number
2
(mm
)
of wires
2.5
3
2.5
3
1.5
4
2.5
4
(3C Flat cable
2)
PU/PUH-P1VGAA.UK~P6YGAA.UK
PU/PUH-P1VGAA
PU/PUH-P5VGAA
(Except PUH-8YE,PUH-10YE)
Polarity
Clockwise : S1-S2-S3
w Pay attention to stripe of yellow and green
Not applicable
(Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Clockwise : S1-S2-S3-Open
w Connect S1 and S3 to the opposite angle
30
.UK~P6YGAA
1
.UK~P6YGAA
2
applicable
2
.
.UK
1
.UK
2
L(m)
6
(50)
2
Not
5
(45)
3
60
4