Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan(drive) o No.
Fan
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor
: D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor
: D.B. 20˚C(68˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
Upper limit
Heating
Lower limit
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 3 phase 415V 50Hz
kW
A
A
kW
W
kW
K/min(CFM)
dB(A)
Cooling
dB(A)
Heating
mm(in.)
W
mm(in.)
D
mm(in.)
H
kg(lbs)
kg(lbs)
L
mm(in.)
Liquid
mm(in.)
Gas
Indoor side
Outdoor side
Height difference
Piping length
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
PUH-P5YGAA.UK
PUH-P5YGAA
.UK
1
Cooling
Heating
3-ph, 50Hz, 380/400/415V(4wires)
4.70
5.04
7.60
8.15
65.5
Linear Expansion Valve
ZR61KCE-TFD-230 (YGAA.UK)
ZR61KCW-TFD-522 (YGAA
3.5
Internal thermostat, thermal relay, HP switch, Discharge thermo
Propeller (direct) o 2
95(3,360)
55
56
4.6(10.1)
1.690 (Ester) 3MAW-POE
Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Outdoor
D.B. -5˚C
11
PUH-P6YGAA.UK
PUH-P6YGAA
Cooling
5.58
9.03
74
Munsell 5Y 7/1
Hermetic
ZR72KCW-TFD-522
.UK)
1
4.2
Line start
38
Plate fin coil
0.07 +0.07
100(3,530)
Reverse cycle
57
58
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
122(269)
R407C
4.9(10.8)
1.774 (Ester) 3MAW-POE
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
.UK
1
Heating
5.91
9.56