Vigilantplant YFGW510 User Manual page 42

Field wireless access point
Hide thumbs Also See for YFGW510:
Table of Contents

Advertisement

l Wiring of antenna extension cable
1.
Use the provided antenna extension cable to connect the antenna connector with the re-
mote antenna. Tighten the connector of the antenna extension cable with a torque of 2 to 3
N∙m. Refer to the specification about the limitation of bend radius when fixing or wiring.
2.
When using two antenna extension cables, the provided arrestor should be inserted be-
tween these cables.
3.
Before the wiring work, confirm the polarities (male/female) of the connectors of antenna,
antenna extension cable, and arrestor.
Tighten the connector of the antenna extension cable with a torque of 2 to 3 N∙m.
Protect by
Self-bonding tape
Housing of YFGW510
Figure C5-8 Wiring for remote antenna
l Ground wiring of arrestor for antenna extension cables
To connect two antenna extension cables, an arrestor for lightning protection is provided. Place
the arrestor between the two antenna extension cables. Connect the grounding cable to the
ground terminal of the arrestor.
Connect the grounding cable to the grounding terminal on the main body. Class D grounding (the
third class grounding) with the grounding resistance of 100 Ω or less is necessary. Do not share
the ground with other devices.
ISA100.11a antenna
Protect by
Self-bonding tape
Antenna Extension Cable 1
Select from Length 3m
<C5. Wiring>
ISA100.11a antenna
Antenna Extension Cable 2
Select from Length 10m
Arrestor
Ground wiring
Antenna Extension Cable 1
Select from Length 3m
Housing of YFGW510
C5-10
FC0508.ai