Available Options - Trane 18-HD64D1-4 Installation Manual

Comfortlink ii
Table of Contents

Advertisement

Installer Setup Menus and Options (continued)
Menu
5.2.3 ADVANCED
ACCESSORIES
5.2.4 ADVANCED
COMFORT
18-HD64D1-4
Setting
 Filtration Type Installed .................................................................... Comm Air Cleaner
 Number of Air Cleaners Installed ..................................................... 1, 2
 Air Cleaner Power Level ................................................................... Low, Medium, High
 Humidifier Installed .......................................................................... Yes, No
 Humidifier Type ................................................................................ Powered/Bypass
 Humidifier Control ............................................................................ RH Control
 Humidifier Fan Action ....................................................................... Humidify without Active Heat Call
 Dehumidifier Installed ...................................................................... No, Yes
 Dehumidifier - Select Relay Panel Aux Contacts ............................. Aux 1
 Dehumidifier Control Options ........................................................... Stand Alone Operation
 Dehumidifier - Run System Fan with Dehumidifier Request ............ No, Yes
 UV Light Installed ............................................................................. None, Yes
 Ventilation Installed .......................................................................... Yes, No
 Ventilation - Select Relay Panel Aux Contacts ................................. Aux 1
 Ventilation - Minimum Outdoor Temperature Allowed ...................... -10F - 50F
 Ventilation - Maximum Outdoor Temperature Allowed ..................... 80F - 110F
 Minimum Ventilation Run Time Per Hour ......................................... 0 - 60 minutes
 Enable Dehumidification .................................................................. Disable
 Dehumidification Overcooling Limit - Degrees ................................. 0, 1, 2, 3
 Control Response Rate ................................................................... Normal
 Aggressive Recovery > 2° Setpoint Change .................................... Disable
 Heating Aggressive Recovery .......................................................... Disable
 Heating Aggressive Recovery - Outdoor Temperature..................... 0 to 70
Warm Air Discharge ......................................................................... Disable

Available Options

Air Cleaner
Media Filter
Steam
Frost Control
Humidify with Active Heat Call Only
Aux 2
Dehumidifier Operation with Active
Call for Cooling Only
Aux 2
Enable
Fast
Enable
Enable
Enable
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Comfortlink iiTzone950ac52za