HindlePower SCRF SERIES Operating And Service Instructions page 2

Float battery charger single phase input
Table of Contents

Advertisement

JF0026-00
MODEL No.
SERIAL No.
1
SMART PART No.
1
(items A-F req'd)
CORE (BB####)
SMART
DWG#
Pos.
PART
CODE
U
UNFILTERED DC OUTPUT
A
F
FILTERED DC OUTPUT
E
BATTERY ELIMINATOR DC OUTPUT FILTERING
120 Vac - 60 Hz INPUT
1
2
208/240 Vac - 60 Hz INPUT
3
220/240 Vac - 50/60 Hz INPUT
4
380/416 Vac - 50/60 Hz INPUT
B
5
480 Vac - 60 Hz INPUT
6
120/208/240 Vac - 60 Hz INPUT (SINGLE PHASE ONLY)
7
208/240/480 Vac - 60 Hz INPUT
0
F
REDUNDANT DC FUSE PROTECTION
C
B
STANDARD DC CIRCUIT BREAKER
C
CUSTOM DC PROTECTION
MANUAL FLOAT / EQUALIZE SWITCH
1
EJ0450
2
EJ0093
MANUAL FLOAT / EQUALIZE SWITCH & IND. LIGHTS
3
EJ0097
0-72 HR. MANUAL EQUALIZE TIMER
D
4
EJ0869
MAN. EQUALIZE TIMER w/ F/E SWITCH & IND. LIGHTS
5
EJ0131
AC FAILURE AUTO-EQUALIZE TIMER & IND. LIGHTS
6
EJ0096
0-72 HR. MANUAL EQUALIZE TIMER & IND. LIGHTS
0
CUSTOM EQUALIZATION
2% ACCURACY 3.5in ANALOG DC METERS
2%
1%
1% ACCURACY 3.5in ANALOG DC METERS
E
SB
1% ACCURACY 4.5in SWITCHBOARD DC METERS
DM
EJ0895
0.1% ACCURACY 3.5in LED DIGITAL DC METERS
CM
CUSTOM DC METERS
STANDARD (COLOR-CODED PVC) WIRING
P
F
SWITCHBOARD INSULATION SYS. (#-CODED) WIRING
H
CB0002
AC POWER FAILURE ALARM & INDICATOR LIGHTS
A
EJ0085
G
C
CUSTOM AC FAILURE ALARM
C1
EJ0837
CASM PC BOARD w/ ONE (1) FORM-C CONTACTS
CASM PC BOARD w/ TWO (2) FORM-C CONTACTS
C2
EJ0837
H
HIGH / LOW DC VOLTAGE ALARM & IND. LIGHTS
HL
EJ0083
CHARGER FAILURE ALARM (NO Adc) & IND. LIGHTS
ZC
EJ0127
HLVA / CFA & IND. LIGHTS (EJ0083 & EJ0127)
HZ
S
EJ0094
GND. DET. SWITCH FOR DC VOLTMETER INDICATION
J
L
EJ0089
GND. DET. IND. LIGHTS w/ GROUND & LAMP TEST
R
EJ0086
GND. DET. RELAYS w/ RESET SWITCH & IND. LIGHTS
K
F
EJ0133
PARALLEL CHGR OPERATION w/ 2% LOAD SHARING
L
H
EJ0592
HIGH DC VOLTAGE CHARGER SHUTDOWN
COMMON ALARM RELAY CONTACTS
R
EJ0141
M
B
EJ0141
COMMON ALARM RELAY CONTACTS w/ BUZZER
C
EJ0967
COMMON ALARM BUZZER FOR CASM PC BOARD
D
EI5030/31
DRIP SHIELDS - STYLE-1A/1B CABINET (EB0220/221)
D
EI5032
DRIP SHIELDS - STYLE-2 CABINET (EB0222)
N
D
EI5033
DRIP SHIELDS - STYLE-3 CABINET (EB0123)
D
EI5034
DRIP SHIELDS - STYLE-4 CABINET (EB0163)
D
EI5035
DRIP SHIELDS - STYLE-5 CABINET (EB0198)
GENERAL SPECIFICATIONS:
Regulation:
+ or - 0.5%
Regulation:
+ or - 0.5%
Regulation:
+ or - 1%
Ambient Temperature Range:
Relative Humidity:
Altitude:
A
B
C
D
E
DESCRIPTION
(30 mV RMS w/BATTERY)
(SINGLE PHASE ONLY)
(SINGLE PHASE ONLY)
(THREE PHASE ONLY)
Vac
Hz INPUT
no-load to full-load
for + or - 10% AC line variation
for combined load, line & temp. variations
0º C to 50º C
up to 95% without condensation
up to 1,000m above sea level
SCR/SCRF Series Battery Charger
Factory-Configured Specifications
F
G
H
J
K
L
M
(X)
DWG#
EJ0088
EJ0095
EJ0120
EJ0121
EJ0123
EJ0134
EJ0135
EJ0137
EJ0138
EJ0143
(CUSTOM)
EJ0145
(F1 / F2)
EJ0155
(F1 / CB2)
EJ0439
EJ0615
EJ082X
EJ1123
EJ1165
EJ1234
EJ1247
EJ1303
EJ1398
EJ5005
EJ5012
EJ5087
EJ5007
-00
EJ5007
-10
X
JH0002
-09
X
JH0002
-07
JH0003
JH0002
-06
JH0002
-03
JH0002
-01
JH0002
-00
JH0004
-01
JH0004
-05
JH0004
-10
ADDITIONAL FEATURES / OPTIONS / NOTES:
INPUT VOLTAGE
FLOAT VOLTAGE
EQUALIZE VOLTAGE
N
1 - Serial Number and Core (BB####) calculated by factory
DESCRIPTION
GROUND DETECTION INDICATOR LIGHTS
2% ACCURACY 3.5in AC VOLTMETER (1PH)
BATTERY DISCHARGE ALARM & IND. LIGHT
2% ACCURACY 3.5in AC VOLTMETER (3PH)
COMMON ALARM BUZZER
2% ACCURACY 3.5in AC AMMETER (1PH)
2% ACCURACY 3.5in AC AMMETER (3PH)
CURRENT LIMIT ALARM & IND. LIGHT (1PH / 3PH)
0-CENTER DC AMMETER FOR BATT/LOAD MONITOR
END OF DISCHARGE ALARM & INDICATOR LIGHT
CABINET HEATER STRIPS
HIGH-LOW AC VOLTAGE ALARM & INDICATOR
OVER-TEMPERATURE ALARM w/ (BUZZER / IND.)
DC POWER ON INDICATOR LIGHT
INTERNAL TEMPERATURE COMPENSATION (PB/NICD)
4-20 mA TRANSDUCER
HIGH AC RIPPLE ALARM w/ INDICATOR LIGHT
AC INPUT LIGHTNING ARRESTOR (1PH / 3PH)
VENT FAN CONTROL RELAY & IND. (FROM EQUALIZE)
BATTERY OPEN ALARM & IND LIGHT
EXTERNAL TEMP COMPENSATION PROBE (PB/NICD)
0-72 HR. MAN. EQ. TIMER & IND. w/ REMOTE EQ.
0-999 HR. MAN. EQUALIZE TIMER w/ SW & IND.
AUXILIARY CONTACTS (TB15-AUX) ON CASM (EJ0837)
SURGE WITHSTAND FILTER (SWC) PER IEEE-472
kAIC AC
kAIC DC CIRCUIT BREAKERS
200 kAIC AC FUSING
(1PH - 2-POLE / 3PH - 3-POLE)
AC
DC
CKT BKR AUX CONTACTS
COPPER GROUND BUS BAR
FUNGUS PROOFING PER CA0004-00
SPECIAL NEMA
CABINET TYPE
in RELAY RACK MOUNTING ASSY.
SPECIAL (FLOOR / WALL) MOUNTING ASSY.
CUSTOM TAG PLATE
ENGRAVED FUNCTIONAL NAMEPLATES
WHITE CHARACTERS ON BLACK BACKGROUND
BLACK CHARACTERS ON WHITE BACKGROUND
PARTS DATA PACKAGE PER MFG. SWITCHBOARD
COPY OF TEST DATA PER NEMA PE5-1985
EXTRA INSTRUCTION MANUALS
CUSTOM DRAWING PACKAGE
CERTIFIED TEST DATA PER NEMA PE5-1985
CERTIFICATE OF CONFORMANCE
BURN-IN OR HEAT-RUN
IN-HOUSE INSPECTION BY OUTSIDE PERSONNEL
EXPORT PACKING PER FS0001-00
CUSTOM PACKING
EXTENDED WARRANTY PER JF5001-00
Vac
Vdc
Vdc
LIGHTS
Adc
Vdc
LIGHTS
w/ LUG(S)
CAD DISK
HOURS

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scr series

Table of Contents