STRAIGHT OUT HORIZONTAL FLUE SYSTEM
Figure 1.7 shows straight out horizontal flue systems
approved for use on this model.
H
MIN. RUN
13.1" (331mm)
H
FIGURE 1.7
Straight Out Horizontal Flueing
ELBOWS
The flue systems installed on this gas heater may
also include one (1), two (2), or three (3) 90 - degree
elbow assemblies.
Figures 1.8 through 1.14 and their corresponding
tables show examples of flue configurations using
elbows. The relationships of vertical rise to hori-
zontal run in flue configurations using elbows MUST
be strictly adhered to.
H
MAX. RUN
24" (610mm)
Heat & Glo • 6000TRSI-AUC • 2078-900 Rev. C • 7/06
V
1´ MIN. (0.30 M)
2´ MIN. (0.61 M)
3´ MIN. (0.91 M)
4´ MIN. (1.22 M)
24´ MAX. (7.32 M)
V
FIGURE 1.8 Flueing with One 90° Elbow
ONE (1) 90-DEGREE ELBOW
Figures 1.8 and 1.9 show an installation using one
(1) 90-degree elbow. Dimension V is listed as MINI-
MUM vertical dimensions and dimension H is listed
as corresponding MAXIMUM horizontal dimensions.
TWO (2) 90-DEGREE ELBOWS
Figures 1.10 and 1.11 show examples of possible in-
stallations using two (2) 90-degree elbows. Dimen-
sion V is listed as MINIMUM vertical dimensions, di-
mension H is listed as MAXIMUM beginning horizon-
tal dimensions, and dimension H+H
responding TOTAL MAXIMUM horizontal dimensions.
THREE (3) 90-DEGREE ELBOWS
Figures 1.12 through 1.14 show examples of possible
installations using three (3) 90-degree elbows. Dimen-
sions V are listed MINIMUM first vertical dimensions
and dimensions H are listed as beginning MAXIMUM
horizontal dimensions. Dimensions H+H
are listed as TOTAL MAXIMUM horizontal dimen-
sions. Dimensions V+V
1
MUM vertical dimensions.
H
2´ MAX. (0.61 M)
4´ MAX. (1.22 M)
6´ MAX. (1.83 M)
8´ MAX. (2.44 M)
8´ MAX. (2.44 M)
H
is listed as cor-
1
and H+H
+H
1
1
are listed as TOTAL MAXI-
2
9