Noritz N-132M Owner's Manual And Installation Manual page 44

Noritz n-132m gas water heater - owner's guide and installation manual
Table of Contents

Advertisement

Clearance Requirements from Vent Terminations to Building Openings
* All clearance requirements are in accordance with ANSI Z21.10.3a-2003 and the National Fuel Gas
Code, ANSI Z223.1.
Maintain the following clearances to any
opening in any building:
• 4' below, 4' horizontally from, or 1' above
any door, operable window, or gravity air
inlet into any building.
3' above any forced air inlet within 10'.
• 1' below, 1' horizontally from, or 1' above
any door, operable window, or gravity air
inlet into any building.
3' above any forced air inlet within 10'.
* For Installations in Canada, clearances are as follows: To windows, doors, & gravity air inlets: 36".
To forced air inlets: 6'. These clearance requirements hold true for all of the above situations: Indoor,
Outdoor w/vent cap.
44
(Noritz vent cap)
Illustration
4'
4'
1'
3'
1'
1'
1'
3'