Quick Connect Multi System Installation

• The Quick Connect Multi System allows the installation of two units together utilizing only a single cord,
eliminating the necessity of a System Controller in such installations.
* If a two unit Multi System will be used with a circulating loop, do not use the Quick Connect method.
For proper operation, install a System Controller in this case. Refer to the System Controller Installation
Manual and pps. 60-63 of this manual for System Controller installation.
The Quick Connect Cord is 6 ft. long. Install the two units 20"-36" apart at the center to ensure
the cord will be able to reach between the units. (See Typical Plumbing diagram).
(If the distance between the two units is too great, not only will the cord not be able to reach,
but the water temperature may also become unstable because of the difference in pipe length
between the two units.)
System Diagram
Quick Connect
Cord
Cord
Connector
Typical Plumbing
Make this distance as short as possible.
* The hot water temperature will
become unstable as the pipe
length increases.
• Insulate the hot water piping to prevent heat loss. Insulate and apply heating materials to the cold
water supply piping to prevent heat loss and freezing of pipes when exposed to excessively cold
temperatures.
Cord
Connector
Terminal Block
Remote Controller Cord
Distance at center: 20-36 in.
Distance on sides
2-18 in.
Union
Union
Quick Connect
Cord
Pressure
Relief
Union
Valve
Shutoff
Gas Valve
Valve
Shutoff Valve
Leave enough clearance around the plumbing
to apply insulation. It will be necessary to add
bends to the piping to ensure that this
clearance is available.
* When connecting 2 devices, use only a
single remote controller.
Note: Connect the remote
controller to only one
Remote Controller
of the devices.
Gas Supply Piping
G
Cold Water Supply
Hot Water
Size the piping to allow for the maximum
flow rates of the units.
Shutoff
Valve
Hot Water
Cold Water