5.
CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
MODEL
: AOU30CLX1, AOU36CLX1
COOLING
Indoor unit is upper
than outdoor unit.
Height
difference H
Indoor unit is under
than outdoor unit
Indoor unit
Connection pipe
 1 Indoor unit is upper than outdoor unit.
30m
99ft.
Ú 1
20m
66ft.
10m
33ft.
7.5m
25ft.
5m
16ft.
0m
0ft.
-5m
-16ft.
Ú 2
-7.5m
-25ft.
-10m
-33ft.
-20m
-66ft.
-30m
-99ft.
Height difference H
H
Outdoor unit
- (02 - 05) -
Pipe length
5m
7.5m
10m
20m
16ft.
25ft.
33ft.
66ft.
-
-
-
-
-
-
0.945
-
-
0.984
0.961
-
0.988
0.988
0.965
0.990
0.992
0.992
0.968
0.998
1.000
1.000
0.976
0.998
1.000
1.000
0.976
-
1.000
1.000
0.976
-
-
1.000
0.976
-
-
-
0.976
-
-
-
Outdoor unit
Connection pipe
 2 Indoor unit is under than outdoor unit.
30m
40m
50m
99ft.
131ft.
164ft.
-
0.932
0.929
0.924
0.947
0.945
0.940
0.963
0.960
0.956
0.967
0.964
0.959
0.971
0.968
0.963
0.979
0.976
0.971
0.979
0.976
0.971
0.979
0.976
0.971
0.979
0.976
0.971
0.979
0.976
0.971
-
0.979
0.976
0.971
H