Prepare the connection cable for the AC voltage
Dimensioning the wire cross-section is the responsibility of the
electrician and depends on the cable length and installation situation.
▪ Min. cross-section 6 mm
▪ Max. cross-section 16 mm
1. Protect the AC voltage connection lines with appropriate fuses; see "Technical data"
on page 86.
2. Strip 18 mm of insulation from the AC voltage connection lines and add wire-end
sleeves.
Connect
The AC connection screw fitting does not have a seal. One of the sup-
plied seals must be used to ensure that the requirements for safety class
IP65 are met.
Installation and user guide for PLATINUM inverters 2100 H, 3000 H, 4000 H, 4600 H
2
2
1. Unscrew the AC screw connection (9)
from the right-hand underside of the
inverter.
2. Route the prepared AC voltage
connection line through the AC screw
connection. Use a seal if required.
3. Feed the AC voltage connection line
into the housing from below.
4. Tighten the AC screw connection.
9
Installation
17