Troubleshooting; Table 18 Troubleshooting Guide - Liebert InteleCool 2 User Manual

Outdoor wall-mount air conditioner, 2 - 5 tons, 50 & 60 hz
Hide thumbs Also See for InteleCool 2:
Table of Contents

Advertisement

8.0
T
ROUBLESHOOTING
Table 18
Troubleshooting guide
Problem
Unit will not start
No cooling
Unit cycles on
high pressure switch
Heat does not operate
Probable Cause
Remedy
No power to unit
Check voltage to input circuit breaker.
Control voltage circuit
Locate short and reset breaker.
breaker open
Shut off by external
thermostat or stat is
Check operation of thermostat.
defective
Low refrigerant
Check with gauges.
charge
Check voltage at contactor. If not present refer to print and
Compressor contactor
determine voltage loss. Check enthalpy sensor for full CCW or D
not pulling in
setting.
No output from
Check operation of stat. Should have voltage output to Y
thermostat
terminal during cooling.
Loss or restriction of
Check condenser blower assembly for proper operation. Check
airflow
for dirty coil or inlet grille restriction.
Defective fan cycling
Switch should make @ 240 PSIG ±10 (1655 kPa ±68.9). (Check
control
settings on adjustable switch when supplied.)
No voltage output
Check stat for proper output to W terminal.
from thermostat
Fusible link blown
Check for open and replace.
Bad contactor
Check for open and replace.
32

Troubleshooting

®
®
Liebert
InteleCool
2