Venting - Harman XXV Pellet Stove Installation & Operating Manual

Xxv pellet stove
Table of Contents

Advertisement

requirements for terminating the Venting
WARNING: Venting terminals must not be recessed
into a wall or siding.
NOTE: Only the Harman Direct Vent Wall Pass-through
(part # 1-00-677077) or PL listed vent pipe wall pass-
throughs and fire stops should be used when venting
through combustible materials.
NOTE: Always take into consideration the effects of
the prevailing wind direction or other wind currents
that may cause flyash and/or smoke when placing the
termination vent.
in addition, the following must be observed:
A. The clearance above grade must be a minimum of
18".
1
B. The clearance to a window or door that may be
opened must be a minimum of 48" to the side, 48" below
the window/door, and 12" above the window/door.
outside air installed, 18" to side or below window/door)
C. A 12" clearance to a permanently closed window is
recommended to prevent condensation on the window.
D. The vertical clearance to a ventilated soffit located
above the terminal within a horizontal distance of 2 feet
(60 cm) from the center-line of the terminal must be a
minimum of 18".
E. The clearance to an unventilated soffit must be a
minimum of 12".
F. The clearance to an outside corner is 11" from center
of pipe.
G. The clearance to an inside corner is 12".
H. A vent must not be installed within 3 feet (90 cm)
above a gas meter/regulator assembly when measured
from the horizontal center-line of the regulator.
I. The clearance to service regulator vent outlet must
be a minimum of 6 feet.
= Vent terminal
8
XXV Pellet Stove
1
= air supply intake

Venting

J. The clearance to a non-mechanical air supply inlet
to the building or the combustion air inlet to any other
appliance must be a minimum of 48".
K. The clearance to a mechanical air supply inlet must
be a minimum of 10 feet.
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a paved
driveway located on public property must be a minimum
of 7 feet.
1,2
M. The clearance under a veranda, porch, deck or
balcony must be a minimum of 12 inches.
applies)
NOTE: The clearance to vegetation and other exterior
combustibles such as mulch is 36" as measured from
the center of the outlet or cap. This 36" radius continues
to grade or a minimum of 7 feet below the outlet.
Certain Canadian and or Local codes or regulations
1
(with
1
may require different clearances.
A vent shall not terminate directly above a side-
2
walk or paved driveway which is located between two
single family dwellings and serves both dwellings.
Only permitted if veranda, porch, deck, or balcony is
3
fully open on a minimum of 2 sides beneath the floor.
nOte: a chimney connector may not pass through
an attic or roof space, closet or similar concealed
space, floor, or ceiling.
nOte: where passage through a wall, or partition of
combustible construction is desired, the installation
1
shall conform to can/cSa-b365. (if in canada)
= area where vent terminal not permitted