Download Print this page

Omron GQ-CRM21 Operation Manual page 54

Componet gateway unit for cc-link

Advertisement

2. Make the following settings on the CC-Link Station Information Dialog Box.
3
• CompoNet communications mode 0, 1, 2, 4, or 5
(1) Set the station type to Ver. 2 Remote device station.
(2) Set the exclusive station count to Exclusive station 4.
(3) Set the expanded cyclic setting as shown below according to the communication mode that was
set on the mode DIP switch.
Communication mode
Communications mode 0
Communications mode 1
Communications mode 2
Communications mode 4
Communications mode 5
• CompoNet communications mode 3 or 6
(1) Set the station type to Ver. 1 Remote device station or Remote device station.
(2) Set the exclusive station count to Exclusive station 4.
3 - 15
(1)
(3)
(2)
CC-Link expanded cyclic setting
Octuple
Quadruple
Double
Quadruple
Double
CompoNet Gateway Unit for CC-Link Operation Manual