Power Specifications - Cisco 6000 Series Site Planning Manual

Network convergence system routers
Hide thumbs Also See for 6000 Series:
Table of Contents

Advertisement

Power Specifications

Table 3-1
Chassis as shipped
Chassis in shipping crate with
pallet
Chassis, fully loaded with
power, fan trays, cards, and
cosmetics
Floor Loading
Chassis in rack footprint
(floor contact area)
Maximum floor loading
Chassis Cooling
Chassis airflow
DC power system airflow
AC power system airflow
Power Specifications
Table 3-2
Power trays
DC power tray
AC power tray
Power Redundancy (N+N)
DC
AC
DC Input
Nominal input voltage
Input current
Cisco Network Convergence System 6000 Series Routers Site Planning Guide
3-2
Cisco NCS 6008 Chassis Specifications (continued)
775 lb (352 kg)
1050 lb (476 kg)
1450 lb (658 kg)
Chassis: 6.9 sq ft (0.64 sq m)
210 lb/sq ft
Two fan trays
70,792 liters per minute
6796 liters per minute
5097 liters per minute
Cisco NCS 6008 Chassis Power Specifications
Either six AC or six DC power trays
(cannot mix AC and DC power trays)
Up to four DC PMs per tray
Up to three AC PMs per tray
Up to 24 power modules can be installed, and only 12 are needed to
be active at any time. This allows support for 12+12 power
redundancy through "A" and "B" battery plant feeds.
Up to 18 power modules can be installed, and only 9 are needed to
be active at any time. This allows support for 9+9 power redundancy
by using two independent AC power sources (9 feeds each).
–48 VDC or –60 VDC
(tolerance range: –40 to –72 VDC)
50 A max at –48 VDC
40 A max at –60 VDC
60 A at –40 VDC (maximum)
Chapter 3