Ac Power Tray Wiring - Cisco 6000 Series Site Planning Manual

Network convergence system routers
Hide thumbs Also See for 6000 Series:
Table of Contents

Advertisement

AC Power Systems
If you have a 3-Phase AC PDU installed, we recommend you install three AC PMs in each AC power
Note
tray to maintain a balanced 3-phase power load.
For detailed AC power specifications, see the

AC Power Tray Wiring

The AC power tray is shipped with AC power cords. Each AC power tray accepts up to three power cords.
Each AC power cord has a different plug type, depending on locale. AC power cords are available for
the locales listed in
Table 2-1
Locale
North America
Europe
United Kingdom
Italy
Australia
Japan
Switzerland
South Africa
Israel
China
Brazil
Cisco Network Convergence System 6000 Series Routers Site Planning Guide
2-8
Each AC PM requires its own single-phase AC input power feed, with it's own circuit breaker.
The AC power receptacles used to plug in the chassis must be the grounding type. The grounding
conductors that connect to the receptacles should connect to protective earth ground at the service
equipment.
AC single-phase input:
Single-phase, 200 to 240 VAC nominal, 50 to 60 Hz.
Each AC power tray contains three IEC-320-C22 receptacles, which can accept up to three
IEC-320-C21 connector female plugs, depending on how many AC PMs are installed in the tray.
The AC power system requires single-phase AC input power to each PM. If you have 3-phase AC
Delta or AC Wye at your equipment, a Cisco NCS 3-phase AC PDU is required to convert 3-phase
AC input power to single-phase AC input power (Cisco PID NCS-PDU-DELTA or
NCS-PDU-WYE). For more information, refer to the
Installation Guide
on Cisco.com.
Table
2-1.
AC Input Power Cord Options
Cisco PID
PWR-CAB-AC-USA=
PWR-CAB-AC-EU=
PWR-CAB-AC-UK=
PWR-CAB-AC-ITA=
PWR-CAB-AC-AUS=
PWR-CAB-AC-JPN=
PWR-CAB-AC-SUI=
PWR-CAB-AC-SA=
PWR-CAB-AC-ISRL=
PWR-CAB-AC-CHN=
PWR-CAB-AC-BRA=
Cisco 3-Phase AC Power Distribution Unit
"Power Specifications" section on page
Plug Rating
20 A/250 VAC
16 A/250 VAC
16 A/250 VAC
16 A/250 VAC
15 A/250 VAC
20 A/250 VAC
16 A/250 VAC
16 A/250 VAC
16 A/250 VAC
16 A/250 VAC
20 A/250 VAC
Chapter 2
Power and Cooling
3-2.
Reference Illustration
Figure 2-5
Figure 2-6
Figure 2-7
Figure 2-8
Figure 2-9
Figure 2-10
Figure 2-11
Figure 2-12
Figure 2-13
Figure 2-14
Figure 2-15
OL-29236-02