ALARMS
ALARM LOG
The Climatic 40 has a log where signifi cant events that stop (alarms) or limit (warnings) the operation of the unit are saved.
In order to enter the Alarm Log menu, proceed as explained in chapter 3 MENU in the paragraph PARAMETERS EDITING MENU,
entering the password 44 instead of 22.
Up to 25 events can be saved, highlighting in order: event code, start hours, start minutes, start day, start month, end hours, end minu-
tes, end day, end month.
START MINUTES
EVENT CODE
START HOURS
START DAYS
START MONTHS
END HOURS
END MINUTES
END DAYS
END MONTHS
WARNING
The alarm log is active and operative only if the clock board is fi tted.
If there are no alarms saved, "noH" is displayed.