Major Components; Main Frame And Electronics; Internal Battery Pack; Figure 1 10 Kva Dual Inverter Gxt 2 (Front And Rear Views) - Liebert GXT2-10000RT208 User Manual

10kva, 60 hz, 120/208/240v
Hide thumbs Also See for GXT2-10000RT208:
Table of Contents

Advertisement

4.0
M
C
AJOR
OMPONENTS
The GXT2-10000RT208 is composed of three major assemblies to provide easier handling, installation
and versatility.
4.1

Main Frame and Electronics

This 6U cabinet arrives without internal batteries to lighten the UPS for easier installation. Once the
cabinet has been placed in its final floor or rack position, the internal batteries may be installed. The
UPS is shipped with standard hardwire terminal blocks for input and output connections.
Figure 1
10 kVA Dual Inverter GXT 2 (front and rear views)
FRONT VIEW
Battery Compartment
(behind center and right bezels); Internal
Battery Pack is shipped loose
(see Section 4.2)
4.2

Internal Battery Pack

The center front bezel may be pulled forward and removed to reveal the battery access plate. The
cover plate can be removed by extracting the three screws at the top of the cover plate and lifting the
plate off. The two internal battery packs are compact assemblies ready to slide into the battery com-
partment after the front battery access plate has been removed. Electrical connection is made with
the two slotted battery connectors.
Figure 2
Internal battery pack and connector
Status Indicators
and Controls
Front Bezels, 3
External Battery
Connectors
Output
Circuit
Breaker
Hardwire
Knockouts
REAR VIEW
7

Major Components

®
Intellislot
Port
DB-9
Communications
Ports, 2
Cooling Fan,
1 of 3
REPO
Switch
UPS/Bypass
Breaker
Input Circuit
Breaker
Battery connector
on front of battery pack