Emerson Copeland Scroll Installation And Reference Manual page 17

Outdoor condensing unit
Hide thumbs Also See for Copeland Scroll:
Table of Contents

Advertisement

Trip to
Fault Type
Set Point
Set based on
Over Current
Compressor
Compressor
intends to start
Electrical
but current
Failure
transformers
sense no
current
*
Minimum 3
Compressor
minutes off time
Rapid Cycling
between starts
Ambient
Ambient sensor
Temperature
reads
Sensor Failure
< -22°F or
(See Table 10)
>145°F
Condensor
Mid-coil sensor
Mid-Coil
reads
Sensor Failure
< -22°F or
(See Table 10)
>145°F
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
Application Engineering
B
U
L
Table 9 Continued
Code
Code
Char.
Char.
1
2
5
2
5
2
2
0
1
8
1
9
L
E
T
Control Board
Actions
-Stop the Unit
-Display over current
trip on diagnostic
-Display waiting to
restart on diagnostic
*
-
Auto start the unit
after 3 minutes
-Lockout unit if 6 trips
in less than 12 hour
-Display over current
lockout on diagnostic
-Display compressor
protector trip on
diagnostic
-Auto Start When
protector resets
*
-
Delay compressor
start, if minimum off
time is less than 3 min
-Display about to turn
on diagnostic
-Display ambient temp
sensors failure on
diagnostic
-Continue to run the
unit on default mode.
-Display mid-coil temp
sensors failure on
diagnostic
-Continue to run the
unit on default mode.
16
I
N
AE5-1377 R2
Auto
Possible Error and
Resets
Solution
-Check rotarty switch,
make sure it is on the
right position according
to the unit model;
-Check oil level through
Auto
compressor sight glass
Start
(Low temp unit only);
-Check accumulator
(Low temp unit only),
inlet should connect
to return gas service
valve.
-Check whether contact
is pull-in? If not, check
wiring of contact coil;
-Check wiring, make
Auto
sure compressor is
Start
connected to contactor,
and is powered;
-Compressor motor
thermal protector trips,
wait until it resets.
-Compressor start
signal is active when
Auto
unit stops; the only
Start
thing needed to do is
wait until the unit starts
-check whether actual
ambient temperature is
out of range;
Run
-Check whether
ambient sensor is
OK and connected to
control board.
-check whether actual
mid-coil temperature is
out of range;
Run
-Check whether mid-
coil sensor is OK and
connected to control
board.