Emerson Copeland Scroll Installation And Reference Manual page 15

Outdoor condensing unit
Hide thumbs Also See for Copeland Scroll:
Table of Contents

Advertisement

Refrigerant Liquid Temperature Valve Capacity Multiplier Correction Factors
0
R-12 Correction
1.60
Factor
R-134a Correction
1.70
Factor
R-22 Correction
1.56
Factor
R-404A/R-507
2.00
Correction Factor
These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an
average evaporator temperature of 0°F. However, they may be used for any evaporator temperature from - 40°F to
+ 40°F since the variation in the actual Factors across this range is insignifi cant.
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
Application Engineering
B
U
L
10
20
30
40
1.54
1.48
1.42
1.36 1.30
1.63
1.56
1.49
1.42 1.36
1.51
1.45
1.40
1.34 1.29
1.90
1.80
1.70
1.60 1.50
Low Pressure Control Settings for XJAM/L Units
Application
XJAL (Low Temp)
XJAM (Medium
Temp)
L
E
T
Table 7
Refrigerant Liquid Temperature °F
50
60
70
80
1.24 1.18 1.12 1.06
1.29 1.21 1.14 1.07
1.23 1.17 1.12 1.06
1.40 1.30 1.20 1.10
Table 8
Control
R404A/R507
Low
0 PSIG Min
Low
17.0 psig Min
14
I
N
AE5-1377 R2
90
100
110
120
1.00
0.94
0.88
1.00
0.93
0.85
1.00
0.94
0.88
1.00
0.90
0.80
130
140
0.82
0.75
0.78
0.71
0.82
0.76
0.70
0.50