Capacity Tables; Cooling Only - Daikin H-Series Engineering Data

H-series cooling only / heat pump split-system room air conditioners
Hide thumbs Also See for H-Series:
Table of Contents

Advertisement

EDUS04-924A

7. Capacity Tables

7.1

Cooling Only

FTXS30HVJU + RKS30HVJU (60 Hz, 230 V)
AFR
20.0
BF
0.23
Temp: Celsius
TC, SHC, PI: kW
INDOOR
EWB
EDB
20.0
°C
°C
TC
SHC
14.0
20.0
6.92
4.97
1.38
16.0
22.0
8.63
5.59
1.85
18.0
25.0
9.83
6.19
2.17
19.4
26.7
10.03
6.43
2.18
22.0
30.0
10.64
6.17
2.20
24.0
32.0
11.04
5.97
2.21
Temp: Fahrenheit
TC, SHC: kBtu/h
PI: kW
INDOOR
EWB
EDB
68.0
°F
°F
TC
SHC
57.2
68.0
23.61
16.97
1.38
60.8
71.6
29.44
19.09
1.85
64.4
77.0
33.53
21.13
2.17
67.0
80.0
34.22
21.94
2.18
71.6
86.0
36.29
21.04
2.20
75.2
89.6
37.68
20.37
2.21
Symbols:
AFR
: Airflow rate
BF
: Bypass factor
EWB
: Entering wet bulb temp.
EDB
: Entering dry bulb temp.
TC
: Total capacity
SHC
: Sensible heating capacity (kW) / (kBtu/h)
PI
: Power input
Room Air Conditioners H-Series
OUTDOOR TEMPERATURE (°CDB)
25.0
PI
TC
SHC
PI
TC
6.92
4.97
1.61
6.92
8.63
5.59
2.18
8.60
9.42
5.99
2.38
9.01
9.62
6.23
2.39
9.21
10.23
5.99
2.40
9.82
10.63
5.81
2.42
10.22
77.0
PI
TC
SHC
PI
TC
23.61
16.97
1.61
23.61
29.44
19.09
2.18
29.35
32.13
20.43
2.38
30.73
32.82
21.26
2.39
31.42
34.90
20.43
2.40
33.50
36.28
19.82
2.42
34.88
(m
/min.)
3
(°C) / (°F)
(°C) / (°F)
(kW) / (kBtu/h)
(kW)
30.0
32.0
SHC
PI
TC
SHC
4.97
1.88
6.92
4.97
5.58
2.57
8.44
5.49
5.78
2.59
8.84
5.70
6.04
2.59
9.05
5.96
5.82
2.61
9.65
5.75
5.65
2.62
10.06
5.59
OUTDOOR TEMPERATURE (°FDB)
86.0
90.0
SHC
PI
TC
SHC
16.97
1.88
23.61
16.97
19.04
2.57
28.79
18.75
19.74
2.59
30.17
19.47
20.59
2.59
30.86
20.33
19.84
2.61
32.94
19.61
19.28
2.62
34.32
19.06
Note:
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat.
2.
shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in
the tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them
with around values in direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25 ft
Level difference : 0 ft
6. Cooling capacity at –15°CDB and 5°FDB.
Temp: Celsius
TC, SHC, PI: kW
60 Hz, 208 - 230 V
INDOOR
OUTDOOR
EWB
EDB
–15 (°CDB)
°C
°C
TC
14.0
20.0
5.49
Temp: Fahrenheit
TC, SHC: kBtu/h
PI: kW
60 Hz, 208 - 230 V
INDOOR
OUTDOOR
EWB
EDB
5 (°FDB)
°F
°F
TC
57.2
68.0
18.73
14.59
3D071130
35.0
PI
TC
SHC
PI
TC
2.00
6.92
4.97
2.20
6.92
2.66
8.19
5.37
2.78
7.78
2.67
8.60
5.59
2.79
8.19
2.68
8.80
5.84
2.80
8.39
2.69
9.41
5.65
2.82
9.00
2.71
9.81
5.49
2.83
9.40
95.0
PI
TC
SHC
PI
TC
2.00
23.61
16.97
2.20
23.61
2.66
27.95
18.31
2.78
26.55
2.67
29.33
19.06
2.79
27.94
2.68
30.00
19.94
2.80
28.63
2.69
32.10
19.26
2.82
30.70
2.71
33.48
18.74
2.83
32.09
SHC
PI
4.28
0.49
SHC
PI
0.49
Capacity Tables
40.0
SHC
PI
4.97
2.46
5.16
2.81
5.39
2.82
5.66
2.83
5.48
2.84
5.34
2.86
104.0
SHC
PI
16.97
2.46
17.61
2.81
18.40
2.82
19.30
2.83
18.69
2.84
18.22
2.86
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents