Application Information Application Information Operating Range Ensure the operating temperature is in allowance range. Cooling Outdoor DB (°C) The use of your air conditioner outside the range of working temperature and humidity can result in serious failure. ° ( Cooling Operation Range DB: Dry Bulb WB: Wet Bulb...
Application Information Installation Guideline INDOOR PRELIMINARY SITE SURVEY a) Electrical supply and installation is to conform to local authority’s (e.g. National Electricity Board) codes and regulations. b) Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply line must be independent of welding transformers which can cause supply fluctuation. c) Ensure that the location is convenient for wiring and piping. MOUNTING a) For ceiling mounted models, locate a position where piping and ducting work can be kept to a minimum.
Page 12
Application Information INDOOR CLEARANCE Mounting Ensure that the overhead supports are strong enough to hold the unit’s weight. Position hanger rods and check for alignment with the unit. Check that hangers are secure and that the base of fan-coil unit is level in the two horizontal directions, taking into account the gradient recommended for drainage flow as shown.
Page 13
Application Information OUTDOOR LOCATION FOR INSTALLATION OF THE CONDENSING UNITS As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected should fulfill the following requirements:- a) Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the unit.
Page 14
Application Information OUTDOOR CLEARANCE SINGLE UNIT PATTERN 1 PATTERN 2 1200 TOP VIEW TOP VIEW RHN80H SERVICE PANEL PATTERN 1 PATTERN 2 PATTERN 1 PATTERN 2 1500 AIR DISCHARGE DIRECTION TOP VIEW TOP VIEW TOP VIEW TOP VIEW WALL / CEILING PATTERN 3 <1500 AIR DISCHARGE GRILL...
Page 15
Cable Size RHN80HMHTY1X RVN100HMHTY1C Indoor 220 - 240V / 1Ph /50Hz + Voltage range** Outdoor 380 - 415V / 3Ph /50Hz + N + Power supply cable size* a) Indoor Unit b) Outdoor Unit c) Total Number of conductors a) Indoor Unit b) Outdoor Unit Recommended fuse/ circuit breaker rating*...
Page 16
Application Information Indoor 380 - 415V / 3Ph /50Hz + N + Voltage range** Outdoor 380 - 415V / 3Ph /50Hz + N + Power supply cable size* a) Indoor Unit b) Outdoor Unit 10.0 Number of conductors a) Indoor Unit b) Outdoor Unit Recommended fuse/ circuit breaker rating*...
Page 17
Indoor 380 - 415V / 3Ph /50Hz + N + Voltage range** Outdoor 380 - 415V / 3Ph /50Hz + N + Power supply cable size* a) Indoor Unit b) Outdoor Unit 10.0 Number of conductors a) Indoor Unit b) Outdoor Unit Recommended fuse/ circuit breaker rating* a) Indoor Unit...
Page 18
FAN MOTOR AND COMPRESSOR PHASE INFORMATION UNIT UNIT UNIT UNIT FBHN80 1 PHASE FBHN100 INDOOR FBHN125/150 3 PHASE FBVN200/250/300/350/400/450/500/600/750 RHN80H RVN100H 1 PHASE OUTDOOR 3 PHASE RVN125H RVN150H 3 PHASE When the pipe length becomes too long, both the capacity and reliability will drop and as the number of bends increases, system piping resistance to the refrigerant increases, thus lowering the cooling capacity.
Sound Data Sound Data Sound Pressure Level Indoor 1/1 Octave Sound Pressure (dB, ref 20μPa) Overall Noise Model Speed (dBA) Criteria 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High FBHN80HBV1X High FBHN100HBV1X High FBHN125HBY1C High FBHN150HBY1C High FBHN200H2BY1C High FBVN250H2BY1C FBVN300H2BY1C High FBVN300H3BY1C...
Sound Data Indoor Model Measuring Location FBVN250H2BY1C FBVN300H2BY1C FBVN300H3BY1C FBVN350H3BY1C UNIT FBVN400H4BY1C FBVN450H3BY1C FBVN500H4BY1C FBVN600H4BY1X FBVN750H5BY1X 2m discharge duct length Free return duct Microphone position: 1m away from every side panel of the unit and 1m above the floor level. (Tested with 2m length duct at the air discharge outlet only) Standard: JIS B 8615 Sound Power Level 1/1 Octave Sound Power Level (dB) ref 1pW Overall...
Selection Process Selection Process Fan Performance Chart Example 1 : The following are the design requirements for FBVN250H2BY1C unit: Model: FBVN250H2BY1C Supply Air Quantity 9000 External Static Pressure Step 1: From the fan curve (at 9000 CFM), Standard operating system; Total Static Pressure Internal Static Pressure, ISP = External Static Pressure, ESP =...
Page 29
Selection Process The following table summarizes the pulley data, motor size used for the FBHN/FBVN series, as manufactured: Pulley Centre Distance, C Motor Motor Model (kW) Horizontal (mm) Vertical (mm) FBHN125HBY1C 1500 FBHN150HBY1C 1500 FBHN200H2BY1C 1420 FBVN250H2BY1C 1440 FBVN300H2BY1C 1440 FBVN300H3BY1C FBVN350H3BY1C 1440...
Page 30
Selection Process Example 1: 7.5 kW 800 RPM 5.5 kW 700 RPM 600 RPM Standard Point 4.0 kW 500 RPM Internal Static Pressure with filter Internal Static Pressure w/o filter 10000 10500 11000 11500 12000 12500 13000 13500 14000 Air Flow...
Page 31
Selection Process FAN PERFORMANCE CURVE FBHN80H (with filter) MEDIUM SUPER HIGH SUPER HIGH HIGH 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 1040 1180 1320 Air Flow...
Page 32
Selection Process FBHN80H (without filter) HIGH MEDIUM SUPER HIGH 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 1040 1180 1320 Air Flow...
Page 33
Selection Process FBHN100H (with filter) MEDIUM HIGH 2000 2200 2400 2600 2800 3000 3200 3400 3600 1570 1320 1450 1700 1080 1210 Air Flow...
Page 34
Selection Process FBHN100H (without filter) MEDIUM HIGH 2000 2200 2400 2600 2800 3000 3200 3400 3600 1700 1570 1320 1450 1080 1210 Air Flow...
Page 47
Engineering & Physical Data Engineering Data – R410A COOLING MODEL INDOOR UNIT FBHN200H2BY1C FBVN250H2BY1C FBVN300H2BY1C FBVN300H3BY1C MODEL OUTDOOR UNIT RVN100HMHTY1C x 2 RVN125HMHTY1C x 2 RVN150HMHTY1C x 2 RVN100HMHTY1C x 3 Btu/h 200,000 250,000 300,000 300,000 NOMINAL COOLING CAPACITY 58,600 73,200 88,000 88,000...
Page 48
Engineering & Physical Data Engineering Data – R410A COOLING MODEL INDOOR UNIT FBVN350H3BY1C FBVN400H4BY1C FBVN450H3BY1C MODEL OUTDOOR UNIT RVN100HMHTY1C RVN125HMHTY1C x 2 RVN100HMHTY1C x 4 RVN150HMHTY1C x 3 Btu/h 350,000 400,000 450,000 NOMINAL COOLING CAPACITY 102,500 117,200 131,900 NOMINAL TOTAL INPUT POWER (COOLING) 34,550 39,330 45,930...
Page 49
Engineering & Physical Data Engineering Data – R410A COOLING MODEL INDOOR UNIT FBVN500H4BY1C FBVN600H4BY1X FBVN750H5BY1X MODEL OUTDOOR UNIT RVN125HMHTY1C x 4 RVN150HMHTY1C x 4 RVN150HMHTY1C x 5 Btu/h 500,000 600,000 750,000 NOMINAL COOLING CAPACITY 146,500 175,850 219,900 NOMINAL TOTAL INPUT POWER (COOLING) 49,990 61,620 78,640...
Performance Data Performance Data Calculation Steps Interpolation method can be used to get the total Solution: cooling capacity, TC and sensible cooling capacity, Based on the Performance Table, SC and power input, PI at those temperatures which 1. Refer to the Indoor DB column, are not stated out in the table.
Page 51
Performance Data (b) Indoor Condition: 25°C DB, 16°C WB By Interpolation Method Outdoor Condition: 35°C DB 25°C – 24°C – 29.18kW ⇒ Outdoor temperature 27°C – 24°C 29.30kW – 29.18kW 35°C ⇒ x = 29.22kW Similarly, = 19.11kW 29.18 18.11 9.99 = 9.99kW 29.30...
Outlines & Dimensions Outlines & Dimensions Indoor Unit Model: FBHN80/100HBV1X FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 80H / 100H 1502 1402 1462 Model / Dimension 80H / 100H 1242 Model / Dimension 80H / 100H Model / Dimension 80H / 100H...
Page 69
Outlines & Dimensions Model: FBVN125/150HBY1C (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 125H / 150H 1640 1540 1600 Model / Dimension 125H / 150H 1377 Model / Dimension 125H / 150H Model / Dimension 125H / 150H...
Page 70
Outlines & Dimensions Model: FBHN125/150HBY1C (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 125H / 150H 1640 1040 1540 1600 Model / Dimension 125H / 150H 1377 Model / Dimension 125H / 150H Model / Dimension 125H / 150H...
Page 71
Outlines & Dimensions Model: FBVN200H2BY1C (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 200H 1794 1624 1854 1894 47.7 754.6 Model / Dimension 200H Model / Dimension 200H...
Page 72
Outlines & Dimensions Model: FBHN200H2BY1C (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 200H 1794 1624 1854 1894 47.7 754.6 Model / Dimension 200H Model / Dimension 200H 1040...
Page 73
Outlines & Dimensions Model: FBVN250/300H2BY1C (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 250H 1766 1636 1826 1866 300H 1766 1636 1826 1866 Model / Dimension 250H 1291 300H 1291 Model / Dimension 250H 1199 1069 1196 1073...
Page 74
Outlines & Dimensions Model: FBHN250/300H2BY1C (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 250H 1766 1636 1826 1866 300H 1766 1636 1826 1866 Model / Dimension 250H 1291 300H 1291 Model / Dimension 250H 1199 1069 1196 1073...
Page 75
Outlines & Dimensions Model: FBVN300H3BY1C (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 300H 1766 1636 1826 1866 Model / Dimension 300H 1291 Model / Dimension 300H 1199 1069 1196 1073 Model / Dimension 300H...
Page 76
Outlines & Dimensions Model: FBHN300H3BY1C (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 300H 1766 1636 1826 1866 Model / Dimension 300H 1291 Model / Dimension 300H 1199 1069 1196 1073 Model / Dimension 300H...
Page 77
Outlines & Dimensions Model: FBVN350H3BY1C (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 350H 2022 1852 2082 2122 Model / Dimension 350H 1546 Model / Dimension 350H 1199 1069 1451 1326 Model / Dimension 350H...
Page 78
Outlines & Dimensions Model: FBHN350H3BY1C (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 350H 2022 1852 2082 2122 Model / Dimension 350H 1546 Model / Dimension 350H 1199 1069 1451 1326 Model / Dimension 350H...
Page 79
Outlines & Dimensions Model: FBVN400H4BY1C (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 400H 2174 2004 2234 2274 1240 Model / Dimension 400H 1546 Model / Dimension 400H 1466 1336 1451 1326 Model / Dimension 400H 96.5 266.5...
Page 80
Outlines & Dimensions Model: FBHN400H4BY1C (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 400H 2174 2004 2234 2274 1240 Model / Dimension 400H 1546 Model / Dimension 400H 1466 1336 1451 1326 Model / Dimension 400H 96.5 266.5...
Page 81
Outlines & Dimensions Model: FBVN450H3BY1C (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 450H 2174 2004 2234 2274 1240 Model / Dimension 450H 1546 Model / Dimension 450H 1466 1336 1451 1326 Model / Dimension 450H...
Page 82
Outlines & Dimensions Model: FBHN450H3BY1C (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 450H 2174 2004 2234 2274 1240 Model / Dimension 450H 1546 Model / Dimension 450H 1466 1336 1451 1326 Model / Dimension 450H...
Page 83
Outlines & Dimensions Model: FBVN500H4BY1C (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 500H 2174 2004 2234 2274 1240 Model / Dimension 500H 1546 Model / Dimension 500H 1466 1336 1451 1326 Model / Dimension 500H...
Page 84
Outlines & Dimensions Model: FBHN500H4BY1C (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 500H 2174 2004 2234 2274 1240 Model / Dimension 500H 1546 Model / Dimension 500H 1466 1336 1451 1326 Model / Dimension 500H...
Page 85
Outlines & Dimensions Model: FBVN600H4BY1X (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 600H 2234 2004 2174 1680 Model / Dimension 600H 1978 1883 1905 1775 Model / Dimension 600H 1758 315.5 Model / Dimension 600H 145.5...
Page 86
Outlines & Dimensions Model: FBHN600H4BY1X (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 600H 2234 2004 2174 1680 Model / Dimension 600H 1918 1883 1905 1775 Model / Dimension 600H 1758 315.5 Model / Dimension 600H 145.5...
Page 87
Outlines & Dimensions Model: FBVN750H5BY1X (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 750H 2234 2004 2174 1680 Model / Dimension 750H 2257 2162 1905 1775 Model / Dimension 750H 2037 Model / Dimension 750H...
Page 88
Outlines & Dimensions Model: FBHN750H5BY1X (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 750H 2234 2004 2174 1680 Model / Dimension 750H 2197 2162 1905 1775 Model / Dimension 750H 2037 Model / Dimension 750H Note: FBHN80-100H models are available in Horizontal Air Discharge as Standard.
Page 89
Outlines & Dimensions Outdoor Unit Model: RHN80HMHTY1X FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 1235 929 568 496 523 869 183...
Page 90
Outlines & Dimensions Model: RVN100/125/150HPY1C (Vertical Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 100H 1067 1006 125H 1030 1067 1002 1006 150H 1030 1166 1002 1096...
Page 91
Outlines & Dimensions Model: RHN100/125/150H (Horizontal Discharge) FOR ILLUSTRATIVE PURPOSES ONLY Note: Dimension in mm Model / Dimension 100H 1006 125H 1030 1006 1002 150H 1030 1096 1002...
Service & Maintenance Service & Maintenance The design concept of the Condensing Unit is such that all servicing can be done from the front and side of the unit. Upon removal of front and side panel, all the electrical “terminal box”, fan and motor assembly and compressor are easily accessible.
Page 100
Service & Maintenance MAINTENANCE For superb performance and lasting durability, please do not forget to conduct proper and regular maintenance. Cleaning The Outdoor Unit Heat Exchanger If you use your air conditioner for prolonged period of time, the outdoor unit heat exchanger will become dirty impairing its function and reducing the performance of the air conditioned.
Troubleshooting Troubleshooting When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply before proceeding with the following troubleshooting procedures. The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which are not listed occur, contact your nearest local dealer.
Page 102
Troubleshooting Phase Sequencer The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase protector) is fitted to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase protector operates, and the unit will not start. This device is located in the control box of the outdoor unit. The following table shows the LED indicator light for phase protector under normal operation and fault conditions.