Takagi T‐KJr2‐IN Installation Manual And Owner's Manual page 7

Gas tankless on‐demand water heater
Table of Contents

Advertisement

 
Installation  and  service  must  be  performed  by  a  qualified  installer  (for 
example,  a  licensed  plumber  or  gas  fitter),  otherwise  the  warranty  will  be 
void. 
WARNING 
The installer (licensed professional) is responsible for the correct installation 
of  the  water  heater  and  for  compliance  with  all  national,  state/provincial, 
and local codes. 
The manufacturer does not recommend installing the water heater in a pit or 
location where gas and water can accumulate.  
 
 
Do not have the vent terminal pointing toward any operating window, door, or 
 
opening into a building.   
Do  not  install  next  to  any  source  of  airborne  debris,  such  as  a  clothes  dryer, 
that  can  cause  debris  to  be  trapped  inside  the  combustion  chamber,  unless 
the system is direct‐vented. 
The  manufacturer  does  not  recommend  installing  the  water  heater  in  an 
attic due to safety issues. If you install the water heater in an attic:
The warranty will not cover damage caused by water quality.  
CAUTION 
Do not install the unit where water, debris, or flammable vapors may get into 
the flue terminal. 
The  manufacturer  recommends  using  the  direct  vent  kit  when  the  water 
heater is installed in a beauty salon. Some chemicals used in a beauty salon 
may affect the flame sensor. Water heater may not work properly. 
Although  the  water  heater  is  designed  to  operate  with  minimal  sound,  the 
manufacturer does not recommend installing the unit on a wall adjacent to a 
bedroom, or a room that is intended for quiet study or meditation, etc. 
Locate your heater close to a drain where water leakage will not do damage to 
surrounding  areas.    As  with  any  water  heating  appliance,  the  potential  for 
leakage at some time in the life of the product does exist.  The manufacturer 
will not be responsible for any water damage that may occur.  If you install a 
drain  pan  under  the  unit,  ensure  that  it  will  not  restrict  the  combustion  air 
flow. 
Make sure the unit will have enough combustion air and proper ventilation.
Keep  the  area  around  the  water  heater  clean.  When  dust  collects  on  the 
flame sensor, the water heater will shut down on an error code.
If  the  above  conditions  cannot  be  met,  use  the  direct  vent  conversion  kit 
 
TK‐TV10.
Place the unit for easy access for service and maintenance.
A  drain  pan,  or  other  means  of  protection  against  water  damage,  is 
required to be installed under the water heater in case of leaks.
Only potable water or potable water / glycol mixtures can be used with this 
water  heater.    Do  not  introduce  pool  or  spa  water,  or  any  chemically 
treated water into the water heater. 
Water  hardness  levels  must  not  exceed  7  grains  per  gallon  (120  ppm)  for 
single  family  domestic  applications  or  more  than  4  grains  per  gallon  (70 
ppm)  for  all  other  types  of  applications.    Water  hardness  leads  to  scale 
formation  and  may  affect/damage  the  water  heater.    Hard  water  scaling 
must be avoided or controlled by proper water treatment. 
Water pH levels must be between 6.5 and 8.5 
Well water must be treated. 
7
 
Page
Installation 
 
 
 
 
 