1. Turn off all electric power to the water heater if service is to be performed. 
 
2. Turn the manual gas valve located on the outside of the unit clockwise   to 
 
 
 
 
The water heater cannot perform properly without sufficient inlet gas pressure. Below are instructions 
on how to check the inlet gas pressure. THIS IS ONLY TO BE DONE BY A LICENSED PROFESSIONAL.  
 
1.
Shut off the manual gas valve on the supply gas line. 
2.
Remove the screw for the pressure port located on 
the gas inlet of the water heater shown in the 
diagram to the right. 
3.
Connect the manometer to the pressure port. 
4.
Re‐open the manual gas valve. Check to see that 
there are no gas leaks.  Open some of the fixtures 
that use the highest flow rate to turn on the water 
heater. 
5.
Check the inlet gas pressure. When the water heater 
is on maximum burn, the manometer should read 
from 5.0" to 10.5" WC for Natural gas, from 8.0" to 
14.0" WC for Propane. 
 
 
 
 
 
‐Measuring inlet gas pressure‐ 
the off position. 
19
 
Page
Installation 