16 AC Power Interrupt Warning [note 6] – When enabled, the thermostat will display an outage warning
when AC power to the thermostat is lost.
17 Short Cycle Protection – Selects the number of minutes the cooling compressor will be locked out after
turning off. This short cycle protection is also active in the heat mode if a heat pump system was selected in
Option 6.
18 Residual Cooling Fan Delay – Selects a delay for the system fan after the cooling compressor has turned
off. This delay will help remove the remaining cool air out of the ductwork providing additional efficiency.
19 Circulating Fan Lock – When enabled, the only user fan options available are ON and CIRC (Circulation).
The AUTO option is not available with this option enabled.
20 Adaptive Recovery Mode (early recovery) [note 7] – Enables or disables the ARM
mode) feature. During ARM, room temperature is recovered by turning on the heating or cooling before the
end of the set back period. The set point temperature is changed to that of the upcoming program temperature.
21 Indoor Remote Sensor Control [note 8] – If a Braeburn
installation, the thermostat will automatically detect the sensor. When an indoor sensor is detected, you may
select between thermostat only (I SENS), remote sensor only (E SENS) or combining the thermostat and the
remote sensor (A SENS). NOTE: This option does not apply to a Braeburn outdoor sensor. When an outdoor
sensor is connected the thermostat automatically recognizes it and no further configuration is necessary.
22 Lockout Security Level – Selects the level of keypad lockout when the thermostat is locked. Level 2 locks
the entire thermostat (including the front reset button). Level 1 locks everything except the SpeedBar
allowing for up and down temperature adjustment. NOTE: The lock code is set in the User Settings mode
(see User Manual).
23 Humidification Mode (6400 only) – Selects between disabling humidification (OFF), dependant control
(DEP) or independent control (IND). The DEP setting controls humidification only during a call for heating.
The IND setting allows humidification output in the heat mode, but does not require a call for heating.
NOTE: It is recommended that the IND setting only be used with systems designed for low air temperature
humidification such as steam humidification. Always ensure the heat exchanger or other system parts are
not exposed to excess water from condensation or other sources. When there is any doubt, use the OFF or
DEP setting.
24 Auto Humidity Set Point Limit (6400 only) [notes 9, 11] – Select between turning the automatic humidity
set point limit to auto (AUTO) or manual (MAN). When AUTO is selected, humidity control is provided auto-
matically based on the outdoor temperature. Selecting MAN allows you to manually control the level
of humidity.
25 Dehumidification (6400 only) – Select between enabling (ON) and disabling (OFF) dehumidification control
(D terminal). For use with a dehumidifier.
26 Auto Changeover Dead Band [note 10] – When auto changeover mode is enabled in option 5 and
selected, the system automatically switches between heating and cooling when the room temperature
meets the normal criteria for either a heating or cooling call. There is a forced separation (dead band)
between the heating and cooling set points so that the systems do not work against each other. This
option selects the amount of this dead band in degrees with the default being 3° F.
27 Compressor Balance Point [notes 4, 11] – Locks out the use of the compressor heat stage when the
outside air temperature is less than the selected setting of 15° F to 50° F (-9° C to 10° C)
28 Auxiliary Heat Balance Point [notes 4, 11] – Locks out the use of the auxiliary heat stage when the
outside air temperature exceeds the selected setting of 70° F to 40° F (21° C to 4° C). NOTE: This balance
point overrides the fossil fuel compressor lockout in option 14. If this option is set to gas and the outdoor
temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.
indoor remote sensor is connected during
®