Mantel Clearance - MHSC SB38 Installation, Operation And Maintenance Manual

Woodburning fireplace
Table of Contents

Advertisement

maNtel clearaNce

Finish the wall with material of your choice. do not install a combustible mantel shelf less
than 18" (457 mm) from the top of the fireplace opening. do not install a mantel face
plate less than 6" (159 mm) from top of fireplace opening. Figure 18. If a combustible ma-
terial is used below a flat mantel shelf, consult your local building codes for minimum clearance
from top of fireplace opening to bottom of mantel shelf.
All joints (top, bottom and sides) where wall or decorative facing material meets fireplace sur-
round must be completely sealed with a noncombustible material. Figure 19
1 "
Ref.
* 18" from top of fireplace opening.
** 6" from top of fireplace opening. (Noncom-
bustible material must separate the black face
surround of the fireplace and any combustible
mantel material)
Figure 18 -
Combustible Mantel Clearances
87D0057
SB38 / SB44 Series Woodburning Fireplace
*
* *
MA81
rev. 8/5/97
rev. 4/18/01
Face Plate
MA81
15