Power — Enclosure
Heat dissipation
NOTE: Heat dissipation is calculated using the
power supply wattage rating.
Maximum inrush current
System Voltage Requirements
NOTE: This system is also designed to be connected to
IT power systems with a phase to phase voltage not
exceeding 230 V.
DC/DC power supply (per power supply module)
Wattage
Connector
Heat dissipation
Maximum inrush current
System Voltage Requirements
NOTE: Heat dissipation is calculated using the power
supply wattage rating.
Physical — Blades
PowerEdge M915
Height
Width
Depth
Weight (maximum)
PowerEdge M910
Height
Width
Depth
Weight (maximum)
PowerEdge M820
Height
Width
10
1200 BTU/hr (maximum)
Under typical input voltage conditions and over the
entire system ambient operating range, the inrush
current may reach 55 A per power supply for 10 ms or
less.
16 A, 200 V AC to 240 V AC, 50 Hz/60 Hz (3000 W power
supply)
16 A, 100 V AC to 240 V AC, 50 Hz/60 Hz (2700 W power
supply)
2700 W
Molex # 394260002 at PSU end,
mating connector Molex # 39422-0012
1205 BTU/hr (maximum)
Under typical input voltage conditions and over the
entire system ambient operating range, the inrush
current may reach 120 A per power supply for 10 ms or
less.
75 A, 48 V DC to 60 V DC
38.5 cm (15.2 inch)
5 cm (2 inch)
48.6 cm (19.2 inch)
12.7 kg (28 lb)
38.5 cm (15.2 inch)
5 cm (2 inch)
48.6 cm (19.2 inch)
13.1 kg (29 lb)
38.5 cm (15.2 inch)
5 cm (2 inch)