GE LanPro 11 U User Manual page 29

Lanpro 11 u 5/6/8/10 kva
Table of Contents

Advertisement

g
LX: OPM_LPA_11U_5K0_10K_1US_V021
Service information on internal timer.
Frequency tracking range: output converter frequency will follow the bypass
frequency within these limits before returning to its own internal frequency.
Standard setting: nominal ±2%. Can be changed into nominal ±4% or ±6%. See
5.3.4 Setup Menu.
No-load shutdown: after a 10 minutes delay the UPS will shut down during utility
failure if the load is < 2%. It will restart after the utility returns or when the unit is
switched off and on again.
Default setting = 1 (active). For disabling this feature see 5.3.4.
Start of the manual Quick Battery Test.
See for more information section 5.4.2 'Quick Battery Test'
Start of the manual Deep Battery Calibration Test.
See for more information sections 5.4.3 'Deep Battery Calibration Test'
Service information on internal UPS components
Service information on internal UPS components
Service information on internal UPS components
Batt.Charger: 0 = off, 1 = float charging; 2 = top charge, 3 = boost charging,
4 = maintenance charge
Duration of latest test performed, hh/mm/ss
The UPS transfers the load to bypass when the keys 'down' (2) and 'enter/reset' (3)
on the front panel are depressed simultaneously for approx. 1 seconds. If the
bypass supply is not within limits, the lower line will show the text 'UNAVAILABLE'.
Service set up information whether the bypass is enabled (default) or disabled. If
disabled: UPS will NOT go to bypass. For disabling the bypass refer to the setup
menu (5.3.4).
Service set up information about the total battery capacity. Information about the
actual battery charge condition. For changing the programmed battery capacity
refer to the setup menu (5.3.4).
Service set up information about frequency tracking speed for the inverter to follow
the bypass frequency, LOW (1Hz/sec.) is the normal value and default. HIGH
(5Hz/sec.) may be suitable if the UPS is connected to a generator with fast
frequency changes and the UPS must be synchronized to prevent alarms. For
changing the lock speed refer to the setup menu (5.3.4).
Service set-up information about the ECO-mode. By pressing 'ENTER/RESET'
the ECO-mode can be enabled or disabled, depending on the actual status. In
this way the load will be supplied by way of the electronic bypass. If the ECO-
mode is disabled the load will be supplied by the inverter. See also 4.5.5.
Service set-up information about the autorestart function. This function can be
switched on or off by pressing 'ENTER/RESET', depending on the actual status.
See also 4.5.6.
28
GE Digital Energy
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents