GE LanPro 11 U User Manual page 12

Lanpro 11 u 5/6/8/10 kva
Table of Contents

Advertisement

g
4.4.1.2
Installation procedure:
input voltage 120Vac (optional, 5-6kVA only), output voltage 120/208/220/230/240Vac.
If a battery extension pack is to be installed, please proceed with section 4.4.5.
If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.4.6.
The numbers between (brackets) refer to figure 19 and 20 in section 5.1.
2
4
5
6
7
see 6.3-4
see 4.4.6 / 7.3
8
9
®
Figure 7. LanPro
Installation procedure 120V input
LX: OPM_LPA_11U_5K0_10K_1US_V021
1.
2.
3.
4.
L
N
5.
6.
7.
8.
9.
1-2 BATTERY
DISCONNECTED
3-4 EMERGENCY
SHUTDOW N
stand-alone,
and RPA card
available:
10. Connect the utility power to the UPS.
11. If hardware modifications were necessary in step 4
5/6-11U:
12. For a quick start proceed with section 5.2 'Start-up'.
11
Mount the levellers: position A to fix the UPS to the floor,
position B to lift the castors from the floor. Please refer to
figure 6, step 1.
Loosen the screws and remove the conduit boxes (17, 2x)
and the cover plate (11).
Make sure that all circuit breakers (7-8-9) are in 'off'
position (down). Please refer to fig. 6, step 3.
Input/output connection:
Lead the input/output cables through the cable inlet. If the
cables come from below (recommended for 8kVA and
10kVA models), you can rotate the cable inlet 90 degrees.
Connect the input wires to the input terminals (11b).
Connect the output wires to the output terminals (11a).
Please refer to section 4.4.2.2 (input) and 4.4.3 (output)
for detailed information.
Re-install the cover plate (11) and the conduit boxes (17,
2x).
An emergency shutdown switch can be connected to
connector J3 on the RS232/Contact Interface Card,
between pins 3 and 4. See section 6.2 for more
information.
For
advanced
communication
RS232/contact interface port (12a) can be connected to a
computer system. See section 6.1 for more information.
The middle 'option slot' (13) allows easy installation of
plug-in cards: SNMP Card or Relay Card. See sections
6.3 and 6.4 for more information.
The right 'option slot' (14) allows easy installation of the
RPA-card (Redundant Parallel Architecture). If the card is
already mounted, and if the unit is intended to be used
stand-alone, a bus terminator (delivered with the unit) has
to be placed in one of the two bus connectors on the card.
If the unit will be part of a parallel system, see sections
4.4.6 and 7.3 for more information.
because the output voltage is different from the default
(208Vac), software modifications should be performed as
well. Proceed with 4.4.4.
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)