Available Input Voltages: Hardware Modifications; Input Voltage 208 Or 240Vac - GE LanPro 11 U User Manual

Lanpro 11 u 5/6/8/10 kva
Table of Contents

Advertisement

g

4.4.2 Available input voltages: hardware modifications

The following input voltages are possible: 208, 240 Vac (see 4.4.2.1) and 120 Vac (see 4.4.2.2)
4.4.2.1

Input voltage 208 or 240Vac.

1.
Input voltage is 208 Vac. This is the factory setting. Proceed with step 3.
2.
Input voltage is 240Vac. In this case the bypass tap on the output transformer must be changed. Please refer
to fig. 8 and 8a. Proceed as follows:
2.1 Remove the blue wire B from faston 74 (connect) and place this wire on faston 72 (park).
2.2 Remove the yellow wire A from faston 61 (park) and place this wire on faston 74 (connect).
Bypass tap factory setting: 208 Volt
PCB1113-D
(park) 61
(park) 72
(connect) 74
73
To manual bypass switch
Bypass tap changed to 240 Volt
PCB1113-D
(park) 61
(park) 72
(connect) 74
73
To manual bypass switch
Figure 8. LanPro
Bypass tap change
3.
Connect the utility supply wires to terminals 6 (L1), 7 (L2) and 8 (equipment grounding conductor). See
figure 9. Ground connection is essential!
If a neutral wire is part of the site wiring provided, we suggest to isolate this wire for future use or other
applications.
gnd
N
4
5
1
2
3
Figure 9. LanPro 5/6/8/10-11U:
Input/output terminals
4.
For the output voltage proceed with 4.4.3.
LX: OPM_LPA_11U_5K0_10K_1US_V021
T1
A
B
14
T1
A
B
14
®
5/6/8/10-11U:
gnd
L1
L2
6
7
8
12
GE Digital Energy
61
65
72
66
74
67
73
®
Figure 8a. LanPro
5/6/8/10-11U:
Rear view
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)