GenRemote CALIBRATION
NOTE: THIS DATA APPLIES ONLY TO
THE OPTIONAL GenRemote CONTROLS
. The unit consists of a Power Logic Module, Display Panel and six conductor shielded Display
Cable. The shielded cable links the display to the module and can be up to 300 feet long. Two
display panels can be daisy chained to one
(1)
module output. The module supports two display
cable outputs allowing for a total of four (4) displays per module. Total allowed cable length per
module, including both display cable outputs, is six-hundred (600') feet.
The logic module
is
powered directly from the generator's cranking battery and consumes less
than
70
milli
amps (7011000 of an amp) when the generator is idle. DC operating voltage can be
12 or 24 volts. The AC generator output can be 115V, 240V, 50/60 Hz, single phase (10) or
three (3 0) phase.
Generator and Engine Monitoring
1.
DC Voltage
-
2.
Oil Pressure
3.
Water Temperature
4.
AC Voltage
5.
AC Current
L-l
6.
AC Current
L-2
7.
Line Frequency
Hz
8.
Engine Hours
Up to 10,000 Hours
9.
Exhaust Over Temperature Alarm
GenRemote is designed to safely interface with the existing engine sensors. The
digital display is easily calibrated to match the readings of the manufacturer supplied
mechanical gauge package.
The GenRemote circuitry is isolated from the generators OEM electrical system. This
assures that GenRemote will not interfere with the manufacturers supplied gauge
package. Electrical isolation also allows normal generator operation should the GenRe-
mote be accidentally disconnected from the generator.
Electrical Hook;'Up
Electrical hookup includes interconnecting with both the generators AC and DC systems.
TheACwires Required: The 115 volt Line One [L-l] is Black Line Two [L-2] is White. The 220 volt
Line - 2 [L-2 ] is BlackwithaRed Stripe. The 220 VACNeutral connection is White and is Not connected
to the GenRemote.
The 220 VAC Generator Neutral is the same as Green Ground wire. The 115/220 VAC Neutral [White
Color] is connected
to
the generator frame.
The DC Wire Harness Supplied Color Code as follows: Green is Ground, White is ESS [Emergency Stop
Switch], White/Black is the Stop Switch, Black is Preheat, Orange is Oil Pressure, Red is Water
Temperature, Yellow is the Exhaust High TemperatureAiarm [marine applications only] andBlack/Red ..
is the Start Button.
, IMPORTANT! The Exhaust High Temp terminal is connected to the ESS terminal when it is not used.
Engines
&
Generators
55