Battery-Module Replacement - Eaton EX 700 Installation And User Manual

Pulsar series uninterruptible power supply
Hide thumbs Also See for EX 700:
Table of Contents

Advertisement

Available languages

Available languages

5. Maintenance
5.2

Battery-Module Replacement

Safety recommendations
The battery can cause electrocution and high short-circuit currents. The following safety cautions are required
before servicing the battery components:
Remove watches, rings, bracelets and all other metal objects from the hands and arms.
w
Use tools with an insulated handle.
w
Battery-module removal
RT m odel
86-86700-00EN A02 - Page 24
A Unscrew the left-hand side of the front panel (two
screws).
B Remove the part.
C Disconnect the battery block by separating the
two connectors (never pull on the wires).
D Remove the metal protection cover in front of the
battery (two screws).
E Turn the connector.
F Pass the connector through the hole.