Input/Output Table; Eev Control Operation; On Board 4-20Ma Suction Pressure Input Control Application; Remote Suction Pressure Application - Resource Data Management Mercury PR0018 User Manual

Mercury
Table of Contents

Advertisement

Mercury Switch User Guide

Input/Output table

Number
I-01
I-02
I-03
I-04
I-05
I-06
I-07
I-08
I-09
I-10
I-11
I-12
I-13
I-14
I-15
I-16
O-01
O-02
O-03
O-04
O-05
O-06
O-07
O-08
O-09
O-10
O-11
O-21
O-31
O-32
O-33
O-34
O-35

EEV Control Operation

Product PR0018-PHI is intended for EEV control on an Island by island basis and can be implemented in two ways.
1.
Using the on board 4-20mA Input to measure the suction pressure going to the island.
2.
Using a remote suction pressure sent from Mercury Plant Controller (PR0600-PACK) on the same IP network. Note this remote
pressure can be shared by more than one Mercury Switch.

On board 4-20mA Suction Pressure Input Control Application

Ensure parameter P-57 is set to "Local".
Configure the remaining parameters.
Connect the suction pressure transducer for the Island to the 4-20mA input on the Mercury Switch.
Ensure the transducer is correctly connected and the mA input selector jumper is in the Pressure position.
Ensure each Mercury case controller has been configured to accept the calculated remote evaporator temperature. See
Mercury user guide for further details.

Remote Suction Pressure Application

Ensure parameter P-57, Evaporator Type, is set to Remote 1 or Remote 2 or Remote 3.
Set parameter P-56, Broadcast ID, to match the ID of the desired Plant Pack Controller.
Configure the remaining parameters.
Configure the desired Plant Pack controller to broadcast the Suction pressure. See RDM Plant Controller PR0600 for further
information on how to broadcast pressure.
Note
If the Plant Controller being read from is set to Bar then the Mercury Switch has to be set for Bar (Type 1 or 3)
If the Controller being read from is set to PSI then the Mercury Switch has to be set for PSI (Type 2 or 4).

To disable local transducer

To disable the local pressure input if it is not being used and stop it alarming transducer fault.
Set P-02 (Span) = 0. This only applies to software version 2.1 or higher.
Warning
Ensure that all power is
switched off before
installing or maintaining
this product
IO
Evap Press
Evap 1 Press
Evap 2 Press
Evap 3 Press
Evap 4 Press
Evap 5 Press
Evap 6 Press
Evap 7 Press
Evap 8 Press
Evap 9 Press
Evap 10 Press
Humidity
Sensor Temp
Remote 1 Pressure
Remote 1 Pressure
Remote 1 Pressure
Evap Temp
Evap 1 Temp
Evap 2 Temp
Evap 3 Temp
Evap 4 Temp
Evap 5 Temp
Evap 6 Temp
Evap 7 Temp
Evap 8 Temp
Evap 9 Temp
Evap 10 Temp
MOP
Trim Level
Remote Trim
Remote 1 Temperature
Remote 2 Temperature
Remote 3 Temperature
Range Bar (Psi)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
0 to 100
-49.0 to 60 (-56.2 to 140.0)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-3.4 to 180.0 (-49.3 to 2610)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
Off ( 0 ) or On (1)
0 to 100 %
Off ( 0 ) or On (1)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
-49.0 to 60 (-56.2 to 140.0)
Revision 2.1D
Units
Bar (Psi)
Bar (Psi)
Bar (Psi)
Bar (Psi)
Bar (Psi)
Bar (Psi)
Bar (Psi)
Bar (Psi)
Bar (Psi)
Bar (Psi)
Bar (Psi)
rH
o
o
C (
F)
Bar (Psi)
Bar (Psi)
Bar (Psi)
o
o
C (
F)
o
o
C (
F)
o
o
C (
F)
o
o
C (
F)
o
o
C (
F)
o
o
C (
F)
o
o
C (
F)
o
o
C (
F)
o
o
C (
F)
o
o
C (
F)
o
o
C (
F)
%
o
o
C (
F)
o
o
C (
F)
o
o
C (
F)
Page 10 of 14