Finishing
A. Mantel Projections
Figure 8.1 shows the minimum vertical dimension of appli-
ance mantels or other combustible projections above the top
front edge of the appliance.
Free Standing Installation
COMBUSTIBLE
STRUCTURE
* This appliance can be installed a minimum of 6 in.
(152 mm) from a combustible structure unless the
structure is vinyl which requires a minimum
clearance of 48 in. (1219 mm)
Figure 11.1 Clearances to Mantels or other Combustibles above Appli-
ance.
14
Heat-N-Glo Lifestyle Collection • Dakota 42/Dakota 42H • 4036-905 Rev I • 10/05
Minimum
Clearance *
84 in.
(2134 mm)
min.
B. Facing Material
WARNING
Fire Risk
Do NOT obstruct air inlet or outlet grilles.
Do NOT modify grilles.
•
Modifying or covering grilles could cause
temperature rise and fi re hazard.
Finishing materials must not interfere with:
•
Air fl ow through grilles or louvers.
•
Operation of louvers or doors.
•
Access for service.
Finish wall material may be combustible, top and sides
Noncombustible Board
0 in.
Sealant Material
Figure 11.2 Noncombustible Facing Diagram
WARNING
Fire Risk
Finish all edges and fronts to clearances and
specifi cations listed in manual.
•
Black metal appliance front may be covered with non-
combustible material only.
•
Do NOT overlap combustible materials onto appliance
front.
•
Install combustible materials up to specifi ed clearances
on top front and side edges.
•
Seal joints between the fi nished wall and appliance
top and sides using only a 300° F minimum sealant.
0 in.
0 in.