Floor Protection - Quadra-Fire Isle Royale 823-0170 Manual

Non-catalytic, top-load, wood heater
Table of Contents

Advertisement

The floor must be non-combustible material, extending beneath heater and to the front, sides and rear as indicated. The
floor must be non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks
and falling embers. A layer of thin brick or ceramic tile over a combustible floor is not sufficient. See Alternate floor protec-
tion calculation sample on page 8.
In USA installations, it is necessary to install a floor protector 16 inches in front and 8 inches to both sides of the loading
door. See *exception below.
In Canada, similar floor protection must be provided 18 inches (457mm) in front and 8 inches (203mm) from the sides and
rear of the stove. See *exception below.
*ExCEPTION: Non combustile floor protections must extend beneath the flue pipe when installed with horizontal venting
and extend 2 inches (51mm) beyond each side.
Fuel loading door
16" from glass - std legs
36-3/4"
Minimum
USA Installations
September 1, 2008
Isle Royale Wood Stove

FLOOR PROTECTION

39-1/4"
Minimum
8"
USA
250-5763C
203mm (8")
203mm
(8")
457mm (18")
1137mm (44-3/4")
Minimum
must extend
length of flue and
2" (51mm)
beyond each
side of pipe
USA - Required
CANADA - Recommended
203mm
1251mm
(8")
(49-1/4")
Minimum
CANADA
Page 7