FLOOR PROTECTION: Floor protector must be noncombustible material, extending beneath heater and to the
front/sides/rear as indicated. The floor must be non-combustible or otherwise adequately protected from radiant
heat given off by the unit and from sparks and falling embers. A layer of thin brick or ceramic tile over a combustible
floor is not sufficient.
In US installations, it is necessary to install a floor protector of 3/8" thick metal clad millboard or equivalent at least 16"
(406mm) in front of glass door and 8" (203mm) to both sides of the fuel loading door. Open the door and measure 8"
(203mm) from the side edge of the opening in the face of the stove. See *exception below.
In Canada, similar floor protection must be provided 18" (457mm) in front and 8" (203mm) from the sides and rear
of the stove. See *exception below.
*EXCEPTION: Non-combustile floor protection must extend beneath the flue pipe when installed with horizontal venting
and extend 2" (51mm) beyond each side.
Fuel loading door
16" from glass
29-5/8"
minimum
203mm (8")
203mm
(8")
457mm (18")
940mm (37-3/8")
minimum
250-6931C November 3, 2004
2100 ACT Millennium Wood Stove

FLOOR PROTECTION

NOTE: Drawings are for illustration purposes only and are not to scale.
3-5/8"
4-3/8"
38"
minimum
8"
USA
203mm
(8")
1248mm
(49-1/8")
minimum
CANADA
USA
33-1/2"
Must extend 2" (51mm) beyond each
side of pipe (shaded area)
USA: REQUIRED
CANADA: RECOMMENDED
R
33-1/2"
Page 7