Technical Specifications
Typical 3 phase 4 wire
current requirements at
200V 240V
Typical 3 phase 5 wire
current requirements at
200V 240V
Maximum Electrical Characteristics
Maximum Electrical Characteristics
Maximum Electrical Characteristics
Maximum Electrical Characteristics
Maximum input power
8,200
(VA)
cabinet marked electrical
AC input power-Option
200 240 VAC phase to neutral, 5 wire, 50/60 Hz
7: 3 phase 5 wire input
AC input power-Option
200 240 VAC phase to phase, 4 wire, 50/60 Hz
6:
3 phase 4 wire input
Maximum current
requirements at 220V
240V:
Option 7: 3 phase
24 A/Phase
5 wire input
Option 6: 3 phase
44 A/Phase
4 wire input
Required power
Option 6: IEC Compliant 4 wire 60A 250V Ph Ph
receptacle
Option 5: IEC Compliant 5 wire 32A 480V Ph Ph
Heat Characteristics
Heat Characteristics
Heat Characteristics
Heat Characteristics
Maximum heat
28,969
dissipation (BTUs/hour)
Typical heat dissipation
20,131
(BTUs/hour)
Site Preparation
Site Preparation
Site Preparation
Site Preparation
Site planning and
Yes
installation included
Depth (mm/inches)
1,220/48.1
Width (mm/inches)
762/30
Height (mm/inches)
1,960/77.2
Weight (Kg/lbs)
500/1,123
Environmental Characteristics
Environmental Characteristics
Environmental Characteristics
Environmental Characteristics
Acoustics
65 dB
Operating temperature
+20°C to +30°C
Non operating
-40°C to +70°C
temperature
Maximum rate of
20°C/hour
temperature change
Operating relative
15% to 80% @ 30°C
humidity
Operating altitude
0 3.1 km (0 10,000 ft)
Non operating altitude
0 4.6 km (0 15,000 ft)
DA - 11717
Worldwide — Version 35 — December 6, 2006
HP Integrity Superdome Servers 16- processor, 32-
HP Integrity Superdome Servers 16- processor, 32-
HP Integrity Superdome Servers 16- processor, 32-
HP Integrity Superdome Servers 16- processor, 32-
processor, and 64- processor Systems
processor, and 64- processor Systems
processor, and 64- processor Systems
processor, and 64- processor Systems
17A/Phase
29A/Phase
10A/Phase
17A/Phase
12,196
24 A/Phase
44 A/Phase
41,614
33,439
Yes
1,220/48.1
762/30
1,960/77.2
598/1,343
Two cabinets 29A/Phase
Two cabinets 17A/Phase
24,392
24 A/Phase
44 A/Phase
83,288
66,877
Yes
1,220/48.1
1,524/60
1,960/77.2
1,196/2,685