Technical Specifications
Additional Interface
Cards
Typical Electrical Characteristics by Configuration
Typical Electrical Characteristics by Configuration
Typical Electrical Characteristics by Configuration
Typical Electrical Characteristics by Configuration
AC input power
Typical Input Power
(watts)
dissipation Itanium 2
(watts)
Typical power dissipation
mx2 (watts)
Typical 3 Phase 4Wire
Current requirements at
200V 240V
Typical 3 Phase 5Wire
Current requirements at
200V 240V
Maximum Electrical Characteristics
Maximum Electrical Characteristics
Maximum Electrical Characteristics
Maximum Electrical Characteristics
Maximum Input Power
(VA)
Cabinet Marked Electrical
AC input power-Option
7: 3 phase 5 wire input
AC input power-Option
6: 3 phase 4 wire input
Maximum Current requirements at 220V 240V:
Option 7: 3 phase 5 wire
24 A/Phase
input
Option 6: 3 phase 4 wire
44 A/Phase
input
Required Power
Receptacle-
Heat Characteristics
Heat Characteristics
Heat Characteristics
Heat Characteristics
Maximum Heat
dissipation (BTUs/hour)
Typical Heat dissipation
(BTUs/hour)
Site Preparation
Site Preparation
Site Preparation
Site Preparation
Site planning and
installation included
Depth (mm / inches)
Width (mm / inches)
Height (mm / inches)
Weight (Kg / lbs)
DA - 11717
Worldwide — Version 35 — December 6, 2006
HP Integrity Superdome Servers 16- processor, 32-
HP Integrity Superdome Servers 16- processor, 32-
HP Integrity Superdome Servers 16- processor, 32-
HP Integrity Superdome Servers 16- processor, 32-
8
200 240 VAC, 50/60 Hz 200 240 VAC, 50/60 Hz 200 240 VAC, 50/60 Hz
5,900
4 cells, 32 GB, 4 I/O
chassis with 6 PCI each
5,730
17A / Phase
10A / Phase
8,200
200 240 VAC phase to neutral, 5 wire, 50/60 Hz
200 240 VAC phase to phase, 4 wire, 50/60 Hz
24 A/Phase
44 A/Phase
Option 6: IEC Compliant 4 Wire 60A 250V Ph-Ph
Option 5: IEC Compliant 5 Wire 32A 480VPh-Ph
28,969
20,131
Yes
1,220 / 48.1
762 / 30
1,960 / 77.2
500 / 1,123
processor, and 64- processor Systems
processor, and 64- processor Systems
processor, and 64- processor Systems
processor, and 64- processor Systems
8 -14
9,800
8 cells, 32 GB, 4 I/O
16 cells, 32 GB, 4 I/O
chassis with
6 PCI each
9,490
29A / Phase
17A / Phase
12,196
24 A/Phase
44 A/Phase
41,614
33,439
Yes
1,220 / 48.1
762 / 30
1,960 / 77.2
598 / 1,343
8 -14
19,600
chassis with
6 PCI each
18,980
Two Cabinets 29A /
Phase
Two Cabinets 17A /
Phase
24,392
83,288
66,877
Yes
1,220 / 48.1
1,524 / 60
1,960 / 77.2
1,196 / 2,685