VENTILATION

WARNING: Ventillation holes must be provided in the
structure at the top and bottom to provide ventilation in the
event of a gas leak.
Ventilation holes can be located in a low visibility area and should be protected by
screening material to prevent rodents and insects from entering the structure. Air holes
will also help dry moisture.
Note: These drawings are only a reference.
Cross ventilation must be incorporated in the supporting structure. We recommend
a minimum of 100 square inches (254 square cm )of venting per side.
Vents should be on two sides of the structure.
The above drawings are for reference only.
Location of the vents should be from the center, outward.
Locate the vents at both the bottom of the structure and at the top of the structure.
The bottom vents should be as close to ground level as possible. Make sure the
vent area is not blocked by interior supports of the structure.
We recommend vents with screens.
Access doors to the structure are not considered vents.
Clean the vents periodically.
DANGER: Failure to follow recommended minimum venting
instructions can cause gas to collect in the structure in the
event of a gas leak. This may result in a fire or an explosion
which can cause serious bodily injury or death, and damage
to property.
WWW.WEBER.COM
®
GAS SUPPLY