Silencing Audible Alarms; Manual Battery Test - CyberPower OLS1000E User Manual

Ups models ols1000e; ols1000exl; ols1500e; ols1500exl; ols2000e; ols2000exl; ols3000e; ols3000exl
Table of Contents

Advertisement

Configure Submenu
Output Voltage
Output Frequency
ECO Mode *
Bypass Mode **
Converter Mode
EPO/ROO***
EBM Number****
*) This function would be set as 0% when Converter Mode is enabled.
**) UPS has no bypass when Converter Mode is enabled.
*** ROO (Remote On/Off): If ROO is anabled, UPS can be turn on/off by the ROO port. If ROO port is disconnected, UPS
will be turned off. If ROO port is connected, UPS will be turned on when the utility is normal
****) UPS cannot detect the numbers of external battery automatically, so manual input from user is necessary.
Note: The manual settings programming mode can ONLY be invoked while UPS is in Bypass mode or Standby mode. To
make UPS on Standby mode, connect utility power to UPS and do not turn on UPS.

SILENCING AUDIBLE ALARMS

Press the "ENTER" button on simultaneously for 5 seconds to disable or enable the alarm system while in battery mode.
Note: Some audible alarms (Over Temperature, Fan Fail, etc.) can't be silenced.

MANUAL BATTERY TEST

Press the "ENTER" button simultaneously for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or
converter mode.
LCD SETUP FUNCTIONS
Available Settings
= [208V] [220V] [230V] [240V]
= [50Hz][60Hz]
[0%] (Disable) [10%][15%] (Enable)
[DIS] (Disable) [ENA] (Enable)
[DIS] (Disable) [ENA] (Enable)
[EPo] [Roo]
[0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10](for –E models, the
maximum number is 3 )
Default Setting
230V
50Hz
0%
Enable
Disable
EPO
0(for –E models) / 1 (for –EXL models)
Copyright © 2012 CyberPower Systems, Inc.
1