Specifications; Mcs-200 Specifications - HP MCS-200 User Manual

Modular cooling system 200
Table of Contents

Advertisement

Specifications

MCS-200 specifications

Item
Voltage
Maximum height
(including the rack)
Maximum width
(including the rack)
Maximum depth
(including the rack and
rack handle)
Maximum shipping
height (on skid)
Maximum shipping
width (on skid)
Maximum shipping
depth (on skid)
Net weight (including
the empty rack)
Shipping Weight (gross
with packaging)
Effective cooling
Rated current maximum 230 VAC - 18 Amps
Steady state current
with maximum fans
Cooling medium
Prefuse
Minimum
recommended water
inlet temperature
Permissible operating
pressure pmax
Maximum operating
noise level
NOTE:
temperature of 42°C (107°F), chilled water temperature of 10°C (50°F), and cold air temperature
of 20°C (68°F).
Specification
230 VAC +/- 10%, 50 Hz and 277 VAC +/- 10%, 60 Hz
200.7 cm (79 in)
90.4 cm (35.6 in) maximum
151 cm (59.5 in) (Depth includes rear extension)
228.5 cm (90.0 in)
122.0 cm (48.0 in)
182.9 cm (72.0 in)
478 kg (1,054 lb) Weight includes rear extension, which
weighs 30 kg (67 lb).
732 kg (1,614 lb) Weight includes rear extension, which
weighs 30 kg (67 lb).
50 kW at 124 l/min (32.8 US gal/min)
(L42W10, L20)
230 VAC - 13.0 Amps
water
20A
7°C (45°F)
8 bar (116 psi)
79 dB(A)
The abbreviation L42W10, L20 is part of the type plate information and stands for hot air
Specifications 57