Type of message
Solution:
Verify the water supply and that the MCS-200 unit is receiving water.
1.
Verify that the water pressure delta is accurate.
2.
Verify that the water flow loss emergency door opening temperature threshold is not less than 5°C
3.
(41°F) above or more than 20°C (68°F) above the Server Intake Temperature Set Point.
Adjust the temperature in the Server Intake Temperature Set Point or the Water Flow Loss Emergency
4.
Door Opening Temperature Threshold fields to prevent false alarms.
IMPORTANT:
Setting the temperature thresholds too low might cause the MCS unit to shut down.
Emergency Door Opening due to High Temperature (35/36/38°C) (95/97/100°F)
Indicators
Operator display alarm message
Web interface alarm message
Condition
Modules or sensors
SNMP notification
Type of message
Solution:
Verify the water supply and that the MCS-200 unit is receiving water.
1.
Verify that the High Temperature Emergency Door Opening Threshold is not less than 5°C (41°F) above
2.
or more than 20°C (68°F) above the Server Intake Temperature Set Point, or that it is not below the
Water Flow Loss Emergency Door Opening Temperature Threshold.
Adjust the temperature in the Server Intake Temperature Set Point or the Water Flow Loss Emergency
3.
Door Opening Temperature Threshold fields to prevent false alarms.
IMPORTANT:
Setting the temperature thresholds too low might cause the MCS unit to shut down.
The condensation pump has exceeded x cycles
Indicators
Operator display alarm message
Web interface alarm message
Meaning
Critical
Alarm
Use caution when entering temperatures in the Emergency Door Opening fields.
Meaning
Emergency Door, Heat
Emergency Door Opening due to High Temperature (35/36/38°C)
(95/97/100°F)
The interface alarm message displays the temperatures of the fans so that
you can see which temperature has been exceeded and had caused the
alarm.
The High Temperature Emergency Door Opening Threshold has been
exceeded.
Server Intake Temperature
Critical
Alarm
Use caution when entering temperatures in the Emergency Door Opening fields.
Meaning
Excessive moisture
The condensation pump has exceeded x cycles
Operator display 51