Indicators
Condition
Modules or sensors
SNMP notification
Type of message
Solution:
To determine the cause, look for leaks or condensation.
1.
If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Cycles
2.
Warning Threshold field.
IMPORTANT:
fields. Be sure to determine the proper default settings to prevent false alarms, without masking
problems with the MCS.
Default settings will vary, depending on the humidity level of your data center and the heat load
generated by the equipment in the MCS.
The condensation pump has run more than x seconds
Indicators
Meaning
Excessive moisture
Operator display alarm
message
The condensation pump has run more than x seconds
Web interface alarm
message
The water level has exceeded the permissible level of the condensation pump sensor.
Condition
Condensation pump sensor
Modules or sensors
Warning
SNMP notification
Warning
Type of message
Solution:
To determine the cause, look for leaks or condensation.
1.
If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Running
2.
Time Warning Threshold field.
IMPORTANT:
fields. Be sure to determine the proper default settings to prevent false alarms, without masking
problems with the MCS.
Default settings will vary, depending on the humidity level of your data center and the heat load
generated by the equipment in the MCS.
NOTE:
A 24-hour clock starts when the condensation pump runs for the first time in more than 24
hours. A warning is issued if either the cycle threshold or pump running time is exceeded within
the 24-hour window. The clock stops and the counters are reset to zero for warning purposes if the
thresholds are not exceeded within 24 hours after the last time the condensation pump runs.
Meaning
The water level has exceeded the permissible level of the condensation
pump sensor.
Condensation pump sensor
Warning
Warning
Use caution when entering temperatures in the Condensation Pump Threshold
Use caution when entering temperatures in the Condensation Pump Threshold
Operator display 52