HP MCS-200 User Manual page 50

Modular cooling system 200
Table of Contents

Advertisement

Temperature below threshold (Low Temperature Threshold field)
Indicators
Operator display alarm message
Web interface alarm message
Condition
Sensors
SNMP notification
Type of message
Solution:
Verify water flow matches specifications required for heat load.
1.
Verify whether the water temperature is below the expected range.
2.
Adjust the temperature assigned in the web interface Intake Temp tab Low Temperature Threshold field.
3.
Contact your building supervisor.
4.
Temperature above threshold (Warning Temperature Threshold field)
Indicators
Operator display alarm message
Web interface alarm message
Condition
Modules or sensors
SNMP notification
Type of message
Solution:
Verify water flow matches specifications required for heat load.
1.
Verify whether the water temperature is above the expected range.
2.
Adjust the temperature assigned in the web interface Intake Temp tab Warning Temperature Threshold
3.
field.
Contact your building supervisor.
4.
Emergency Door Opening due to Water Flow Loss (0 l/min; 36/34/35°C) (0 gal/min; 97/93/95°F)
Indicators
Operator display alarm message
Web interface alarm message
Condition
Modules or sensors
Meaning
Temperature too low
Temperature too low
The average server air temperature is lower than the temperature assigned
in the web interface Intake Temp tab Low Temperature Threshold field.
Air temperature sensor
Warning
Warning
Meaning
Temperature Warning
Temperature Warning
Average server air temperature is above the temperature assigned in the
web interface Intake Temp tab Warning Temperature Threshold field
Air temperature sensor
Warning
Warning
Meaning
Emergency Door, Flow
Emergency Door Opening due to Water Flow Loss (0 l/min; 36/34/35°C)
(0 gal/min; 97/93/95°F)
The interface alarm message displays the temperatures of the fans so that
you can see which temperature has been exceeded and caused the alarm.
The water flow loss emergency door opening temperature threshold has
been exceeded or the water flow is less than 2 l/min (.5283 gal/min).
Server Intake Temperature, Water Flow Meter