START UP SERVICE

Environmental Monitor Service, Inc. is available to assist you, call our service department at (203) 935-0102 or fax
(203) 634-6663 for details and to schedule start up.

Verifying instrument operation and configuration

Alignment procedure must be completed as outlined in Section 2.
Power applied to both the control unit and the sensors for a minimum of 30 Minutes before any adjustments are
attempted.
Observe the front panel LED's and confirm the red Operate and the green RUN LED's are on. Press the ACK
button to confirm NO ALM'S message is displayed. Press the DIS button until OPACITY % is displayed.

EDIT KEYS

All data entry, editing, and diagnostics are accomplished with four EDIT
keys behind the hinged cover.

FACTORY O.P.L.R. DISPLAY

Under the flip down door, press the EDIT (ESC) button (the red Edit
(ESC) LED will light). The message display will read
the ENTER key, then the EDIT  key or hold and scroll down until the
Display reads "OPLR Read Only". Press the ENTER key the OPLR is
displayed. This is a read only block and cannot change the OPLR of the
system. It is intended for a convenient place to record the OPLR. The OPLR
is factory set and cannot be changed in the field. If an OPLR change is
required contact the factory for return authorization number and shipping
instructions.

QUICK MENU

 Alarm Set Point
 Alarm Time Delay
 Auto Cal Cycle Time
 Zero Cal Value
 Span Cal Value
 OPLR Read Only
QUICK MENU
In % opacity
In Seconds
In hours
In % opacity
In % opacity
XX.XX
23
+19999
. Press
MESSAGE
ACK
PV
SP
OUT
EDIT
EDIT
ENTER
"Edit
Value"
Light
"Scroll
Menu"
light
DIS
Moves
Message
Cursor
AUTO
MAN
REM
LOC
EDIT
(ESC)
Keys
EDIT
Hinged
Cover

Advertisement

Table of Contents
loading

Table of Contents