I N S TA L L AT I O N
I N S T R U C T I O N S
E L E C T R I C A L
R E Q U I R E M E N T S
Verify that power is disconnected from
electrical box before proceeding.
Maximum connected load: 5.2 kW for
30" (762) and 36" (914) ranges; 10.2 kW for
48" (1219) and 60" (1524) ranges.
Required power supply: 240V / 208V /
30A / 60Hz for 30" (762) and 36" (914)
ranges; 240V / 208V / 50A / 60Hz for 48" (1219)
and 60" (1524) ranges.
Minimum supply wire size: L1 and L2 – 12
AWG, neutral – 16 AWG, ground – 12 AWG
for 30" (762) and 36" (914) ranges.
Minimum supply wire size: L1 and L2 – 8
AWG, neutral – 12 AWG, ground – 10 AWG
for 48" (1219) and 60" (1524) ranges.
Total electric rating: 5.2 kW at 240V,
4.5 kW at 208V for 30" (762) and 36" (914)
ranges; 10.2 kW at 240V, 8.8 kW at 208V for
48" (1219) and 60" (1524) ranges.
Total amps: 22 amps for 30" (762) and 36"
(914) ranges; 43 amps for 48" (1219) and 60"
(1524) ranges.
The terminal block on the rear of the range
allows for a 3-wire or 4-wire installation. For a
4-wire installation, the ground strap from the
unit to the terminal block must be cut. Two
concentric knockouts are provided to allow for
permanent or cordset wiring of the unit.
You must follow all National Electrical Code
regulations. In addition, be aware of local
codes and ordinances when installing your
service.
Dimensions in parentheses are in
millimeters unless otherwise specified.
F O U R - W I R E E L E C T R I C A L S Y S T E M
To connect to a four-wire electrical system,
follow these steps:
Cut or remove the ground strap on the
terminal block.
Connect the white appliance wire to the
neutral (white) supply wire on the terminal
block.
Connect the black appliance wire to the
black (L1) power supply wire on the
terminal block.
Connect the red appliance wire to the red
(L2) power supply wire on the terminal
block.
Connect the ground appliance wire to the
green/ground house grounding wire on the
terminal block.
T H R E E - W I R E E L E C T R I C A L S Y S T E M
To connect to a three-wire electrical system,
follow these steps: Connecting the ground
appliance wire to the neutral (white) supply
wire (where local codes permit).
Connect the ground and white appliance
wires to the neutral (white) supply wire on
the terminal block.
Connect the black appliance wire to the
black (L1) power supply wire on the
terminal block.
Connect the red appliance wire to the red
(L2) power supply wire on the terminal
block.
I M P O R TA N T
N O T E
You must follow
all National
Electrical Code
regulations. In
addition, be aware
of local codes and
ordinances when
installing your
service.
15