ELECTRIC
MODELS
- U.S.
and Canada
A 120/240
volt, 60 Hz AC approved
electrical
service
fused through
a dedicated
30 ampere fuse or circuit break-
er on both sides of the line is required.
If a power cord is used, the cord should
be plugged
into a dedicated
30 ampere
receptacle.
U.S.
ELECTRIC
MODELS
The power cord is NOT provided
with U.S. electric
model dryers.
IMPORTANT:
When permitted
by local codes, the dryer electrical
supply may be connected
by means of a
new power supply cord kit, marked for use with clothes
dryer, that is U.L. listed, rated at 120/240
volts
minimum,
30 amperes
with three
No. 10 copper
wire conductors
terminated
with closed loop terminals,
open-end
spade
lugs with turned
up ends or with tinned
leads.
Do not reuse a power
supply cord from an old dryer.
The power cord electric
supply wiring
must be retained
at the dryer cabinet
with a suitable
UL listed strain relief.
If the dryer is to be installed
in an area where
local codes
do not permit grounding
through
neutral,
only a
4 conductor
power cord, rated and terminated
as above, may be used.
120/208
Volt Electrical
Systems:
A U.S. electric
washer/dryer
must be converted
if it is to operate
on a 120/208
volt electrical
system.
A heating
element
conversion
kit is available
for the dryer (see Accessories).
CANADIAN
ELECTRIC
MODELS
All Canadian
models
are shipped
with the power
cord attached.
[It is not permissible
to convert
a dryer in Canada
to 208
volts.J
Additional Instructions for Export Models
(not U.S. or Canada)
Contact
the distributor
that sold the appliance
or: Maytag
International,
8700 W. Bryn Mawr Avenue,
Chicago,
Illinois USA
60631,773-714-0100,
for information
on product,
shipping
damage,
replacement
parts and
accessories.
Maytag
models
manufactured
for operation
on 60 Hz AC are not designed
for use on 50 Hz AC
electrical
service
and conversion
of the product
from 60 to 50 Hz operation
is not recommended.
For
additional
information
on 50 Hz products,
contact
Maytag
International.
The electric
service
requirements
can be found on the data label located on the front of the dryer behind the
door.
EXPORT
ELECTRIC
MODELS
Export electric
models are manufactured
for operation
on either 230/240
volt, 50 Hz or 220 volt, 60 Hz
approved
electric service.
A two-wire
approved
electrical
service
with a 30 ampere
fuse or circuit breaker
is
required.
The dryer must be properly
grounded
with a ground wire.
IMPORTANT:
When
permitted
by local codes, the dryer electrical
supply
may be connected
by means of a
new power supply cord kit, marked for use with clothes
dryers, that is agency
listed, rated at 240 volts
minimum,
30 amperes
with two No. 10 copper
wire conductors
terminated
with closed
loop terminals,
open-end
spade
lugs with turned
up ends or with tinned
leads.
Do not reuse
a power supply
cord from
an old dryer.
The power cord or electric
supply wiring
must be
retained
at the dryer cabinet with a suitable
agency
listed strain relief.
Page 7