KitchenAid KERS807SBL04 Installation Instructions Manual page 11

30" (76.2 cm) freestanding and slide-in electric ranges
Table of Contents

Advertisement

Available languages

Available languages

4-wire connection:
Power Supply Cord
Use this method for:
New branch-circuit
installations (1996 NEC)
Mobile homes
Recreational vehicles
In an area where local codes prohibit grounding through the
neutral.
1. Cut out and remove part of the metal ground strap (B).
5. Use 3/8"nut driver to connect the neutral (white) wire to the
center terminal block post with one of the 10-32 hex nuts.
F
B
C
A
i
B
C
A. Metal ground strap
B. Discard
C. Ground-link
screw
2. Use a Phillips screwdriver to remove the ground-link
screw
from the back of the range. Save the ground-link
screw and
the end of the ground link under the screw.
3. Feed the power supply cord through the strain relief on the
cord/conduit
plate on bottom of range. Allow enough slack to
easily attach the wiring to the terminal block.
B
A. 10-32 hex nut
B. Ground-link
screw
C. Line 2 (red)
D
D. Green ground wire
E. Neutral (center) wire
F. Line 1 (black)
6. Connect line 2 (red) and line 1 (black) wires to the outer
terminal block posts with 10-32 hex nuts.
7. Securely tighten hex nuts.
NOTE: For power supply cord replacement, use only a power
cord rated at 250 volts minimum, 40 amps or 50 amps that is
marked for use with nominal 13/8"(3.5 cm) diameter
connection opening, with ring terminals and marked for use
with ranges.
8. Tighten strain relief screws.
9. Replace terminal block access cover.
3-wire connection:
Power Supply Cord
Use this method only if local codes permit connecting chassis
ground conductor to neutral wire of power supply cord.
1. Feed the power supply cord through the strain relief on the
cord/conduit
plate on bottom of range. Allow enough slack to
easily attach the wiring to the terminal block.
A
......................
4=
A. Terminal block
B. Ground-link
screw
C. UL listed strain relief
D. Power supply cord wires
Use a Phillips screwdriver to connect the green ground wire
from the power supply cord to the range with the ground-link
screw and ground-link
section. The ground wire must be
attached first.
A. Terminal block
B. Ground-link
screw
C. UL listed strain relief
D. Power supply cord wires - large opening
11