WARNING REGARDING EARTHING GROUND:
o
This equipment shall be connected to the DC supply
system earthing electrode conductor or to a bonding
jumper from an earthing terminal bar or bus to which the
DC supply system earthing electrode is connected.
o
This equipment shall be located in the same immediate
area (such as adjacent cabinets) as any other equipment
that has a connection between the earthed conductor of
the same DC supply circuit and the earthing conductor,
and also the point of earthing of the DC system. The DC
system shall not be earthed elsewhere.
o
The DC supply source is to be located within the same
premises as this equipment.
o
There shall be no switching or disconnecting devices in
the earthed circuit conductor between the DC source and
the earthing electrode conductor.
The standard operating temperature of this equipment is 0 to 50 degrees C. If
installed in a closed or multi-module rack assembly, the operating ambient
temperature of the rack must not exceed the maximum rated 50 degrees C. See
specifications on page 10 for wide temperature ranges.
Installation of the equipment should be such that the air flow in the front, back
and side vents of the chassis are not compromised or restricted.
Never use this equipment to carry any weight except its own. Never use it as a
shelf to support weight of other equipment.