Trained Service Technician's Regular Maintenance - Beckett AFII85 Installation Manual

Oil burner afii series types 'hlx' & 'fbx' air tube combinations voltage: 120 volts ac/60 hz
Table of Contents

Advertisement

Trained
Service
Technician's
Regular
Maintenance
.
• If the burner locks out on safety during bleed-
ing, reset the safety switch and complete the
bleeding procedure. Note -- Electronic safety
switches can be reset immediately; others may
require a three- to five-minute wait.
• If burner stops after flame is established, addi-
tional bleeding is probably required. Repeat the
bleeding procedure until the pump is primed
and a flame is established when the vent fitting
is closed.
• For R7184 primary controls, see Technician's
Quick Reference Guide, part number 61351 or
61465, for special pump priming sequence.
• Prepare for combustion tests by drilling a 1/4"
sampling hole in the flue pipe between the ap-
pliance and the barometric draft regulator.
Initial air adjustment --
Using a smoke tester,
adjust the air dial (and change firing pin on HLX
ATC's, if necessary) to obtain a clean flame. Now
the additional combustion tests with instruments
can be made.
Set combustion
with instruments
1. Allow the burner to run for approximately
5 to 10
minutes.
.
.
Set the stack or over-fire draft to the level speci-
fied by the appliance manufacturer.
Natural Draft Applications;
typically over-fire
draft is -0.01" or -0.02" w.c.
• Direct Venting;
typically may not require draft
adjustment.
• High Efficiency/Positive
PressureApplianc-
es; also vary from traditional appliances (see
manufacturer's
recommendations).
Follow these four steps to properly adjust the
burner:
Step 1:
Adjust the air dial until a trace of smoke is
achieved.
Step 2:
At the trace of smoke level, measure the
CO2 (or 02) . This is the vital reference point for
further adjustments.
Example: 13.5% CO2 (2.6%
02)
Step 3:
Increase the air to reduce the CO2 by 1.5
to 2 percentage points. (02 will be increased by
approximately 2.0 to 2.7 percentage points.)
Ex-
ample: Reduce CO2 from 13.5% to 11.5% (2.6%
to 5.3% 02).
Step
Ii
4:
Recheck smoke level. It should be Zero.
This procedure provides a margin of
reserve air to accommodate
variable
conditions.
If the draft level has changed, recheck the
smoke and CO2 levels and readjust the burner
if necessary
.
.
Once combustion is set, tighten all fasteners on
air dial, rear access door, and escutcheon plate.
Start and stop the burner several times to ensure
satisfactory
operation. Test the primary control
and all other appliance safety controls to verify
that they function according to the manufactur-
er's specifications.
Trained
Service
Technician's
Regular
Maintenance
Annual
Professional
Ser-
vice Required
Tampering
with or making
incorrect
adjustments
could lead to equip-
ment malfunction
and result
in
asphyxiation,
explosion
or fire.
• Do not tamper with the burner or controls or
make any adjustments unless you are a trained
and qualified service technician.
• To ensure continued reliable operation, a quali-
fied service technician must service this burner
annually.
• More frequent service intervals may be required
in dusty or adverse environments.
• Operation and adjustmentofthe
burnerrequires
technical training and skillful use of combustion
test instruments and other test equipment.
The following
guidelines
are provided
for routine
maintenance.
CI Replace the oil supply line filter. The line filter
cartridge must be replaced to avoid contamina-
tion of the fuel unit and nozzle.
CI Inspect the oil supply system. All fittings should
be leak-tight. The supply lines should be free of
water, sludge and other restrictions.
CI Remove and clean the pump strainer if appli-
cable.
CI Replace the nozzle with an exact replacement
as specified by the appliance manufacturer.
CI Clean and inspect the electrodes for damage,
replacing any that are cracked or chipped.
CI Check
electrode
tip settings.
Replace
elec-
trodes if tips are rounded.
CI Inspect the igniter cables and connections.
CI Clean the cad cell grid surface, if necessary.
CI Inspect all gaskets. Replace any that are dam-
aged or would fail to seal adequately.
CI Inspect the combustion head and air tube. Re-
move any carbon or foreign matter. Replace all
damaged units with exact parts.
CI Clean the blower wheel, air inlet, air guide,
burner housing and nozzle line assembly of
any lint or foreign material.
Page 10
RWB 6104 BAFII R01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afii100Afii150

Table of Contents